APPENDIX
Sequence program
OFF
RISEND instruction
OFF
Completion device
OFF
Status display
device at completion
OFF
RYn
OFF
RXn
App - 21
(c) There are two types of interlock signals for the RISEND instruction: the
completion device (D) and the status display device at completion (D)+1.
1) Completion device
Turns ON in the END processing of the scan where the RISEND
instruction is completed, and turns OFF in the next END processing.
2) Status display device at completion
Turns ON and OFF depending on the completion status of the RISEND
instruction.
Normal completion : Stays OFF and does not change.
Abnormal completion: Turns ON in the END processing of the scan
END processing
END processing
ON
(d) Multiple dedicated instructions cannot be executed for the same station.
Since it takes several scans until the processing of the dedicated instruction
is completed, execute the next dedicated instruction after the completion
device has turned ON.
The next dedicated instruction executed before completion of the previously
executed dedicated instruction is ignored.
(e) The basic number of steps of the RISEND instruction is 10 steps.
(f)
The send buffer assignment is performed using the "Station information
setting" of the network parameters of the GX Developer. For more details,
see Section 6.2.
where the RISEND instruction is completed, and
turns OFF in the next END processing.
Execution completion of
the RISEND instruction
Send completion
Receive completion
MELSEC-Q
END processing END processing
ON
ON Abnormal
completion
Normal
completion
1 scan
App - 21