806f050c-18810003 Memory Logging Limit Reached for [PhysicalMemoryElementName] on Subsystem
[MemoryElementName].
Explanation: DIMM 3 of MEU memory logging limit has been reached.
May also be shown as 806f050c18810003 or 0x806f050c18810003
Severity: Warning
Alert Category: Warning
Serviceable: No
CIM Information: Prefix: PLAT and ID: 0144
SNMP Trap ID: 43
Automatically notify Support: No
User response:
1. Refer to TIP H212293 for minimum code level.
2. Check the IBM support site for an applicable retain tip or firmware update that applies to this memory error.
3. At the next maintenance opportunity, swap affected DIMM (as indicated by the Light path diagnostics) to a
different memory channel or CPU (check this document and the Installation and User's Guide for population
requirements for sparing/paring modes).
4. If PFA re-occurs (on the same DIMM) replace the affected DIMM as indicated by the Light path diagnostics.
5. If problem stays with the same DIMM connector, inspect DIMM connector for foreign material. If damaged,
replace th MEU.
6. Replace the CPU board.
806f050c-18810004 Memory Logging Limit Reached for [PhysicalMemoryElementName] on Subsystem
[MemoryElementName].
Explanation: DIMM 4 of MEU memory logging limit has been reached.
May also be shown as 806f050c18810004 or 0x806f050c18810004
Severity: Warning
Alert Category: Warning
Serviceable: No
CIM Information: Prefix: PLAT and ID: 0144
SNMP Trap ID: 43
Automatically notify Support: No
User response:
1. Refer to TIP H212293 for minimum code level.
2. Check the IBM support site for an applicable retain tip or firmware update that applies to this memory error.
3. At the next maintenance opportunity, swap affected DIMM (as indicated by the Light path diagnostics) to a
different memory channel or CPU (check this document and the Installation and User's Guide for population
requirements for sparing/paring modes).
4. If PFA re-occurs (on the same DIMM) replace the affected DIMM as indicated by the Light path diagnostics.
5. If problem stays with the same DIMM connector, inspect DIMM connector for foreign material. If damaged,
replace th MEU.
6. Replace the CPU board.
806f050c-18810003 • 806f050c-18810004
Appendix B. Integrated management module error messages
661