Product Certifications
August 2016
Temperature Code T3C; Suitable for Class
I, Zone 0; Class I Division 2 Groups A, B, C
and D, T5; Suitable for Class I Zone 2,
Group IIC; Type 4X; Factory Sealed; Single
Seal (See drawing 03031-1053)
E6
Canada Explosionproof, Dust-Ignitionproof and
Division 2
Certificate: 1053834
Standards: ANSI/ISA 12.27.01-2003,
CSA Std. C22.2 No. 30 -M1986,
CSA Std. C22.2 No.142-M1987,
CSA Std. C22.2 No. 213 - M1987
Markings: Explosionproof Class I, Division 1, Groups
B, C and D; Suitable for Class I, Zone 1,
Group IIB+H2, T5; Dust-Ignitionproof for
Class II and Class III, Division 1, Groups E, F
and G; Class I, Division 2, Groups A, B, C
and D; Suitable for Class I Zone 2, Group
IIC; Type 4X; Factory Sealed; Single Seal
(See drawing 03031-1053)
B.1.4 Europe
E8
ATEX Flameproof and Dust
Certificate: KEMA00ATEX2013X;
Baseefa11ATEX0275X
Standards: EN60079-0:2012 + A11:2013,
EN60079-1:2007, EN60079-26:2007,
EN60079-31:2009
Markings:
II 1/2 G Ex d IIC T6/T5 Ga/Gb,
T6(-50 °C
T5(-50 °C
II 1 D Ex ta IIIC T 95 °C T
(-20 °C
T
Table B-1. Process Temperature
Temperature class
T6
T5
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm.
Installation, maintenance and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. For information on the dimensions of the flameproof
joints the manufacturer shall be contacted.
3. Some variants of the equipment have reduced
markings on the nameplate. Refer to the Certificate
for full equipment marking.
140
T
+65 °C),
a
T
+80 °C);
a
105 °C Da
500
+85 °C)
a
Process temperature
-50 °C to +65 °C
-50 °C to +80 °C
I1
ATEX Intrinsic Safety and Dust
Certificate: BAS97ATEX1089X; Baseefa11ATEX0275X
Standards: EN60079-0:2012, EN60079-11:2012,
EN60079-31:2009
Markings: HART:
T5(-60 °C
T4(-60 °C
Fieldbus/PROFIBUS:
T4(-60 °C
DUST:
T
105 °C Da (-20 °C
500
Table B-2. Input Parameters
HART
Parameter
Voltage U
i
Current I
200 mA
i
Power P
0.9 W
i
Capacitance C
0.012
i
Inductance L
0 mH
i
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the
500 V insulation test required by clause 6.3.12 of
EN60079-11:2012. This must be taken into account
when installing the apparatus.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however
care should be taken to protect it from impact or
abrasion if located in Zone 0.
3. Some variants of the equipment have reduced
markings on the nameplate. Refer to the Certificate
for full equipment marking.
IA
ATEX FISCO
Certificate: BAS97ATEX1089X
Standards: EN60079-0:2012, EN60079-11:2009
Markings:
II 1 G Ex ia IIC T4 Ga
(-60 °C
T
Table B-3. Input Parameters
Parameter
Voltage U
i
Current I
i
Power P
i
Capacitance C
i
Inductance L
i
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the
500 V insulation test required by clause 6.3.12 of
EN60079-11:2012. This must be taken into account
when installing the apparatus.
Reference Manual
00809-0100-4797, Rev DA
II 1 G Ex ia IIC T5/T4 Ga,
T
+40 °C),
a
T
+70 °C)
a
II 1 G Ex ia IIC Ga
T
+60 °C)
a
II 1 D Ex ta IIIC T 95 °C
T
+85 °C)
a
Fieldbus/PROFIBUS
30 V
30 V
300 mA
1.3 W
μ
μ
F
0
F
0 mH
+60 °C)
a
FISCO
17.5 V
380 mA
5.32 W
<5 nF
μ
<10
H
Product Certifications