Product Certifications
August 2016
3. It is a condition of manufacture that only the
apparatus fitted with housing, covers and sensor
module housing made out of stainless steel are used
in Group I applications.
N7
IECEx Type n
Certificate: IECEx BAS 09.0077X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T5 Gc (-40 °C
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the
500 V insulation test required by IEC60079-15. This
must be taken into account when installing the
apparatus.
B.1.6 Brazil
E2
INMETRO Flameproof
Certificate: UL-BR 13.0643X
Standards: ABNT NBR IEC60079-0:2008 + Errata
1:2011, ABNT NBR IEC60079-1:2009 +
Errata 1:2011, ABNT NBR
IEC60079-26:2008 + Errata 1:2008
Markings: Ex d IIC T6/T5 Ga/Gb,
T6(-50 °C
T5(-50 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm.
Installation, maintenance and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. In case of repair, contact the manufacturer for
information on the dimensions of the flameproof
joints.
3. The capacitance of the wrap around label, being
1.6 nF, exceeds the limit in Table 9 of ABNT NBR IEC
60079-0. The user shall determine suitability for the
specific application.
I2
INMETRO Intrinsic Safety
Certificate: UL-BR 13.0584X
Standards: ABNT NBR IEC60079-0:2008 + Errata
1:2011, ABNT NBR IEC60079-11:2009
Markings: HART: Ex ia IIC T5/T4 Ga,
T5(-60 °C
T4(-60 °C
Fieldbus/PROFIBUS: Ex ia IIC T4 Ga
(-60 °C
T
142
T
+70 °C)
a
T
+65 °C),
a
T
+80 °C)
a
T
+40 °C),
a
T
+70 °C)
a
+60 °C)
a
Table B-7. Input Parameters
HART
Parameter
Voltage U
i
Current I
200 mA
i
Power P
0.9 W
i
Capacitance C
0.012
i
Inductance L
0 mH
i
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V
transient suppressor, it is not capable of withstanding
the 500 V insulation test required by ABNT NBR IRC
60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however,
care should be taken to protect it from impact or
abrasion if located in Zone 0.
IB
INMETRO FISCO
Certificate: UL-BR 13.0584X
Standards: ABNT NBR IEC60079-0:2008 + Errata
1:2011, ABNT NBR IEC60079-11:2009
Markings: Ex ia IIC T4 Ga (-60 °C
Table B-8. Input Parameters
Parameter
Voltage U
i
Current I
i
Power P
i
Capacitance C
i
Inductance L
i
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V
transient suppressor, it is not capable of withstanding
the 500 V insulation test required by ABNT NBR IEC
60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however,
care should be taken to protect it from impact or
abrasion if located in Zone 0.
Reference Manual
00809-0100-4797, Rev DA
Fieldbus/PROFIBUS
30 V
30 V
300 mA
1.3 W
μ
μ
F
0
F
0 mH
T
+60 °C)
a
FISCO
17.5 V
380 mA
5.32 W
<5 nF
μ
<10
H
Product Certifications