b. In the Basic Setup >> Units >> Output Signal (Analog Input Block) field, enter upper and
c. From the Basic Setup >> Units >> Output Signal (Analog Input Block) >>
5. Cycle power after configuration is complete.
6. Verify all parameters have written to the device correctly.
2.6.2

Level configuration

LOI
To configure the Rosemount 3051 for Level measurement with the LOI, select UNITS >>
LEVEL. When configuring Level units, the following parameters are set:
Measurement type: Level
Linearization: None
During unit configuration, the user defines scaling and units per the application
requirements. See
scaling help.
Class two master
To configure the transmitter for a level application, use the level output in the Transducer
Block.
Level configuration using class two master
1. From the Basic Setup >> Units >> Primary Value >> Primary Value Type dropdown, select
Level.
2. Select units.
Note
Level units in steps 2a, 2b, and
using the LOI.
a. From the Basic Setup >> Units >> Primary Value >> Scale In (Transducer Block) >> Unit
b. From the Basic Setup >> Units >> Primary Value >> Scale Out (Transducer Block) >> Unit
c. From the Basic Setup >> Units >> Output Signal (Analog Input Block) >> Unit (Output)
3. Enter scaling.
Note
Scaling is done in the Transducer Block.
a. In the Basic Setup >> Units >> Primary Value >> Scale In (Transducer Block) field,
1.
Measurement Type Level drives Linearization to None (Characterization > Characterization Type > No Linearization) when downloaded
to the device. Re-upload configuration to verify new Characterization Type.
Configuration
lower values (this value should correspond to the unit selected in Step 2c).
Characterization Type dropdown, select No Linearization.
Appendix D: PROFIBUS® Block Information
(1)
2c
(Secondary Value 1) dropdown, select engineering unit.
(PV) dropdown, select engineering unit.
dropdown, select engineering unit.
enter upper and lower values (this value should correspond to the unit selected in
step 2a).
must match. Set units in the Al Block in offline mode or
Configuration
August 2016
for detailed menu for further
9