Adjusting Frequency Reference Using Pulse Train Inputs

The frequency reference can be adjusted when b1-01 (Reference Selection) is set to 4 (Pulse Train Input). Set
the pulse frequency in constant H6-02 to 100% reference, and then adjust the gain and bias accordingly using
H6-03 and H6-04.
Related Constants
Con-
stant
Number
Pulse train
H6-01
input function
selection
Pulse train
H6-02
input scaling
Pulse train
H6-03
input gain
Pulse train
H6-04
input bias
Pulse train
H6-05
input filter
time
The following diagram shows the method for adjusting the frequency reference using pulse inputs.
RP
Pulse
-40
6
Name
Description
0: Frequency reference
1: PID feedback value
2: PID target value
Set the number of pulses in
hertz, taking the reference to be
100%.
Set the input gain level as a per-
cent when the pulse train set in
H6-02 is input.
Set the input bias when the pulse
train is 0.
Set the pulse train input primary
delay filter time constant in sec-
onds.
Filter
1
Cycle
measurement
1+sT
H6-05
Scaling using H6-02
Fig 6.33 Frequency Reference Adjustments Using Pulse Train Inputs
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 2
0
No
A
1000 to
1440 Hz
Yes
A
32000
0.0 to
100.0%
Yes
A
1000.0
-100.0
0.0%
Yes
A
to 100.0
0.00 to
0.10 s
Yes
A
2.00
Gain and bias
H6-03
H6-04
0
100
MEMO
Open
BUS
V/f
Flux
Loop
Regis-
with
Vec-
Vec-
ter
PG
tor
tor
A
A
A
42CH
A
A
A
42DH
A
A
A
42EH
A
A
A
42FH
A
A
A
430H
=0
Master speed
frequency
=1
PID feedback
PID target value
=2
H6-01