Using the Mail Send Function
CX-
Setting
Programmer
Unit Setup
Tab
Send Mail
Trigger type
(Send mail
conditions 1 to
8)
Interval time
Mail address (desti-
nation)
Send user data
Send Error Log infor-
mation
Send status informa-
tion
IO memory data
Attached file name
Note
20
Setting requirement
One type must be selected.
• Rising edge of the Mail Send Switch: Select the Software
switch Option.
• Change in specified word's value: Select the Word value
change Option and specify the Area, Address, Value, and
State.
• Change in specified bit's status: Select the Bit value change
Option and specify the Area, Address, Bit, and State.
• Entry in Ethernet Unit's error log: Select the ETN condition
Option.
• Change in CPU Unit status: Select the CPU condition Option.
• Sending mail at periodic intervals: Select the Periodic timer
Option.
Required when the trigger type is set to Word value change, Bit
value change, or Periodic timer.
Required.
Required to send a user-set ASCII message in the e-mail body.
Required to send the error log information in the e-mail body.
Required to send the Ethernet Unit's status in the e-mail body.
Required when the Send file data/IO memory data Option has
been selected and a data file is being attached (IO data (IOM),
IO data (CSV), or IO data (TXT)).
Required when the Send file data/IO memory data Option has
been selected.
(1) Make POP settings when the Use POP before SMTP Option was select-
ed in the SMTP Tab.
(2) Make DNS settings when the Server specification type is set to Host
name in the SMTP or POP Tab.
Section 2-4
Reference
page 21