Automatic Clock Adjustment Error Processing
Note
96
Error
Meaning
code
1st byte
03C6
Clock data
0001: Clock data could not
write error
be refreshed because of a
CPU Unit error.
0002: Clock data could not
be refreshed because the
CPU Unit could not write
clock data in that operation
mode.
(1) For details on other error log information, refer to the Operation Manual,
Construction of Networks: SECTION 8 Troubleshooting.
(2) An error will occur in the following CPU Units when the automatic clock
adjustment function is executed under the conditions shown in the table.
CPU Unit
CPU Units manufactured on or
before January 31, 2003 (lot num-
bers 030131 or earlier):
@@
CJ1G-CPU
H
@@
CJ1H-CPU
H
@@
CS1G-CPU
H
@@
CS1H-CPU
H
(3) The manufacturing date can be determined from the lot number on the
side or top corner of the CPU Unit.
(4) The lot numbers are as follows:
YYMMDDnnnn, in which YY indicates the last two digits of the year, MM
the month, DD the day, and nnnn the serial number.
Detailed error code
2nd byte
Clear the CPU
Unit error.
The automatic
clock adjustment
function is not
supported by cer-
tain CPU Units
(models, lot num-
bers) if they are in
RUN or MONI-
TOR mode.
(See note.)
When the CPU execution mode is set to other
than normal mode (priority peripheral servicing
mode, parallel processing with synchronous
memory access mode, or parallel processing
with asynchronous memory access mode).
AND
When the CPU Unit operating mode is set to
RUN or MONITOR mode.