Omron CS CJ1W-ETN21 Operation Manual page 146

Sysmac cs and cj series ethernet units construction of applications
Hide thumbs Also See for CS CJ1W-ETN21:
Table of Contents

Advertisement

Using Socket Services by Manipulating Dedicated Control Bits
TCP Socket Passive Open Request
TCP Socket Active Open Request
122
Response
code
0000
Normal end
0105
Local IP address setting error.
0302
CPU Unit error; cannot execute.
1100
TCP socket number is not 1 to 8 or local TCP port number is 0.
110C
Request Switch turned ON during other processing.
220F
Specified socket is already open or already processing an open
request.
2211
Unit is busy; cannot execute.
2606
Specified socket is already open as UDP socket; cannot open TCP
socket.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
003E
Internal buffer cannot be obtained due to high reception traffic
(ENOBUFS).
0042
An error occurred. (EMSGSIZE).
(See note.)
0045
Error in communications with remote node (ECONNABORTED).
0049
The same TCP port number has been specified more than once
(EADDRINUSE).
004A
Error (ECONNREFUSED).
(See note.)
004B
Error in communications with remote node (ECONNRESET).
(See note.)
004E
Remote IP address parameter error (ENETUNREACH).
(See note.)
0051
Remote IP address parameter error (EHOSTUNREACH).
(See note.)
0053
Error in communications with remote node (ETIMEDOUT) or remote
node does not exist.
0066
Internal memory cannot be obtained; cannot execute.
0080
Open request timed out.
0081
The specified socket was closed during open processing.
0082
Connection could not be established with specified remote node.
Note These response codes will be returned only on large, multilevel networks.
Response
code
0000
Normal end
0105
Local IP address setting error.
0302
CPU Unit error; cannot execute.
1100
TCP socket number is not 1 to 8 or local TCP port number is 0.
110C
Request Switch turned ON during other processing.
220F
Specified socket is already open or already processing an open
request.
2211
Unit is busy; cannot execute.
2606
Specified socket is already open as UDP socket; cannot open TCP
socket.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
Section 6-7
Meaning
Meaning