Attached File Transfer Times - Omron CS CJ1W-ETN21 Operation Manual

Sysmac cs and cj series ethernet units construction of applications
Hide thumbs Also See for CS CJ1W-ETN21:
Table of Contents

Advertisement

Attached File Transfer Times

3-7

Attached File Transfer Times

Access Times for CS1 and
CJ1 CPU Units
Access Times for CS1-H
and CJ1-H CPU Units
Note
62
When sending an attached file with the Mail Receive Function, the access
time can be as long as 30 or 40 minutes for a very large file. The following
tables show how long the CPU Unit's memory will be accessed by the Ether-
net Unit (how long the Accessing Memory/Receiving Mail Flag will be ON).
Command
Data size
FileWrite
1 KB
10 KB
100 KB
1 MB
FileRead
1 KB
10 KB
100 KB
1 MB
IOMWrite
1 word
6,000 words
IOMRead
1 word
6,000 words
Command
Data size
FileWrite
1 KB
10 KB
100 KB
1 MB
FileRead
1 KB
10 KB
100 KB
1 MB
IOMWrite
1 word
6,000 words
IOMRead
1 word
6,000 words
(1) The access times for FileWrite and FileRead commands indicate Memo-
ry Card access times.
(2) The access times in the tables above are standard times when the PLC
Setup's "Fixed Peripheral Servicing Time" setting is set to the default val-
ue of 4% of the cycle time.
(3) The attached file transfer time can be reduced by increasing the time al-
lowed for peripheral servicing in the PLC Setup's "Fixed Peripheral Ser-
vicing Time" setting.
CPU Unit's operating mode
PROGRAM
---
10 ms cycle time
0.3 s
1.6 s
1.5 s
9.3 s
13.7 s
90.4 s
160.1 s
1125.4 s
0.2 s
0.9 s
1.0 s
6.3 s
9.2 s
65.9 s
135.2 s
1132.0 s
0.1 s
0.1 s
0.2 s
0.3 s
0.1 s
0.1 s
0.2 s
0.3 s
CPU Unit's operating mode
PROGRAM
---
10 ms cycle time
0.2 s
0.4 s
0.9 s
2.6 s
9.0 s
25.7 s
90.5 s
302.8 s
0.1 s
0.3 s
0.4 s
1.8 s
4.0 s
17.8 s
48.4 s
272.0 s
0.1 s
0.1 s
0.1 s
0.2 s
0.1 s
0.1 s
0.1 s
0.2 s
Section 3-7
RUN
RUN

Hide quick links: