ASSEMBLY AND INSTALLATION
Wall Screws
and Anchors
Snorkel
Termination
Cap
4" Clearance
Gravel
Drain
Window Well
Fig. 35 Snorkel kit installation.
VERTICAL THROUGH-THE-ROOF
APPLICATION/INSTALLATION
For all vertical through-the-roof installations, the supplied
flue restrictors must be installed. Install the flue restrictor
according to the settings shown in the Vertical Through-the-
Roof Installation Flue Restrictor Chart in order to balance
the airflow in and out of the unit and to maintain proper
flame height.
This gas stove has been approved for:
Vertical installations up to 40' (12 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 38
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by
18" (450 mm).
Example: Maximum horizontal length:
No elbows
1 x 45° elbow = 8.5' (2.6 m)
2 x 45° elbows = 7' (2.1 m)
A minimum of an 8' (2.5 m) vertical rise is required.
(Figure 38)
Two sets of 45° elbow offsets may be used within the
vertical sections. From 0 to a maximum of 8' (2.5 m) of
vent pipe can be used between elbows. Figure 38
SLP-HVS supports offsets. This application will require
that you first determine the roof pitch and use the ap-
propriate starter kit. (Refer to Venting Components
2222
Waterproof Seal
Around Pipe
Firestop
RADIANCE
ST653
install snorkel
4/20/01 djt
= 10' (3 m)
list.)
The maximum angular variation allowed in the system
is 270°. Figure 39
For the minimum height of the vent above the highest
point of penetration through the roof refer to Figure 39�
Vertical Through-the-Roof Installation
Flue Restrictor Setting Chart
Vertical Run
8-12 feet of pipe
(2.4 – 3.7 m)
12-40 feet of pipe
(3.7 – 12 m)
ST653
Fig. 36 Flue Restrictor Set at Medium Restriction
Fig. 37 Flue Restrictor Set at Maximum Restriction
Radiance
Direct Vent Gas Heater
®
Restrictor Setting
Medium restriction
Figure 36
Maximum restriction
Figure 37
FP3042
restrictor 75
FP3043
restrictor 100
FP3042
FP3043
20306759