Divert Roof Run-Off; Vertical Side Wall Installation - Vermont Castings Radiance RADVTSCCB Installation And Operating Instructions Manual

Radvt series direct vent gas heater
Hide thumbs Also See for Radiance RADVTSCCB:
Table of Contents

Advertisement

ASSEMBLY AND INSTALLATION

DIVERT ROOF RUN-OFF

HHT recommends, where excessive water run-off is
possible, use of one of the two options shown in Figure
29 to prevent water running off the roof and onto/into the
horizontal termination cap.
Fig. 29 Locate Vent Opening on Wall

VERTICAL SIDE WALL INSTALLATION

NOTE: For all top vent vertical through-the-roof
installations, install the supplied flue restrictors
onto the top edge of the firebox flue adapter
according to the Vertical Side wall Installation Flue
Restrictor Chart.
1. Locate vent opening on the wall. It may be necessary
to first position the stove and measure to obtain hole
location. Depending on whether the wall is combus-
tible or noncombustible, cut opening to size. Figure
30 (For combustible walls first frame in opening.)
Combustible Walls: Cut a 9"H x 9"W (244 x 244 mm) hole
through the exterior wall and frame as shown. Figure 30
Noncombustible Walls: Hole opening must be 7" (178
mm) in diameter.
NOTE: When using flex vent, the opening will have
to be measured according to the 1/2" (13 mm) rise
in 12" (305 mm) vent run.
2020
Install gutter
Install L-shaped
diverter
Radiance
Vent Opening for Combustible Walls
9"
(244 mm)
9"
(244 mm)
Stove Hearth
Opening for Noncombustible Wall
7"
(190 mm)
Fig. 30 Locate Vent Opening on Wall
2. Secure firestop to the inside frame, center in the 9" x
9" vent opening.
VO584-100
3. Place stove into position. Measure the vertical height
Vent Opening
(X) required from the base of the flue collars to the
2/99 djt
center of the wall opening. Figure 31
X
Fig. 31 Vertical Height Requirements
4. Using appropriate length of pipe section(s) attach to
stove by twisting collar.
5. Measure the horizontal length requirement including
a 2" (51 mm) overlap, i.e. from the elbow to the out-
side wall face plus 2" (51 mm) (or the distance re-
quired if installing a second 90° elbow). Figure 32
NOTE: Always install vertical side wall horizontal
venting with a 1/4" rise for every 12" of run.
Direct Vent Gas Heater
®
Framing Detail
Stove Hearth
20306759