Troubleshooting - Vermont Castings Radiance RADVTSCCB Installation And Operating Instructions Manual

Radvt series direct vent gas heater
Hide thumbs Also See for Radiance RADVTSCCB:
Table of Contents

Advertisement

Radiance
Direct Vent Gas Heater
®
TROUBLESHOOTING THE GAS CONTROL SYSTEM (RADVT MODELS)
NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the "On" position.
Symptom
Spark Ignitor will not
1. Defective or mis-
light
2. Defective ignitor
Pilot will not stay
1. Defective pilot gener-
lit after carefully
following lighting
instructions
2. Defective automatic
Pilot burning, no
1. Wall switch or wires
gas to main burner
2. Thermopile may not
3. Plugged burner
4. Defective automatic
Frequent pilot out-
1. Pilot flame may be
age problem
2. Possible blockage of
20306759
SIT NOVA 820 MILLIVOLT VALVE
Possible Causes
1. Using a match, light pilot. If pilot lights, turn off pilot and push the red button
aligned electrode at
pilot
2. With the control knob in the pilot position, push the control knob all the way and
(push button)
1. Check pilot flame. Must impinge on thermocouple/thermopile. NOTE: This
ator (thermocouple),
remote wall switch
2. Turn valve knob to "Pilot". Maintain flow to pilot; millivolt meter should read
valve
1. Check wall switch and wires for proper connections. Jumper wire across termi-
defective
be generating suffi-
cient millivoltage
3. Check burner orifices for debris and remove.
orifice
4. Turn valve knob to "On", place wall switch to "On" millivolt meter should read
valve operator
1. Clean and/or adjust pilot flame for maximum flame impingement on thermopile
too low or blowing
(high) causing the
pilot safety
to drop out
2. Check the vent terminal for blockage (recycling the flue gases)
the vent terminal
again. If pilot will not light - check gap at electrode and pilot-should be 1/8" to
have a strong spark.
hold. Check for spark at electrode and pilot. If no spark to pilot, and electrode
wire is properly connected, replace the battery in the ignitor module and try
again. Refer to Maintenance Section. If the problem still exists, replace the
ignitor module box.
pilot burner assembly utilizes both a thermocouple and a thermopile. The
thermocouple operates the main valve operation (On and Off). Clean and or
adjust pilot for maximum flame impingement on thermopile and thermocouple.
greater than 10mV. If the reading is okay and the pilot does not stay on, replace
the gas valve. NOTE: An interrupter block (not supplied) must be used to
conduct this test.
nals at wall switch, if burner comes on, replace defective wall switch.. If okay,
jumper wires across wall switch wires at valve, if burner comes on, wires are
faulty or connections are bad.
Be sure wire connections form thermopile at gas valve terminals are tight
and thermopile is fully inserted into pilot bracket.
One of the wall switch wires may be grounded. Remove wall switch wires
form valve terminals if pilot now stays lit, trace wall switch wiring for ground.
May be grounded to stove or gas supply.
Check thermopile with millivolt meter. Take reading at thermopile terminals
of gas valve. Should read 250-300 millivolts (minimum 150) while holding
valve knob depressed in pilot position and wall switch "Off". Replace faulty
thermopile if reading is below specified minimum.
greater than 150mV. If the reading is okay and the burner does not come on,
replace the gas valve.
and thermocouple.
OPERATING INSTRUCTIONS
Corrective Action
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents