Fan Motor Or Related Abnormality - Daikin 2MXS40H2V1B Service Manual

Inverter multi for 2 rooms h-series / g-series
Hide thumbs Also See for 2MXS40H2V1B:
Table of Contents

Advertisement

Troubleshooting for RA Indoor Unit
5.3

Fan Motor or Related Abnormality

5.3.1 DC Motor (Wall Mounted Type, Floor Standing Type)
A6
Error Code
Method of Error
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Detection
Error Decision
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
Conditions
Supposed
Causes
161
Disconnection of connector
Foreign matters stuck in the fan
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB
SiBE121123_A
Service Diagnosis