Sa Indoor Unit - Ffq Series - Daikin 2MXS40H2V1B Service Manual

Inverter multi for 2 rooms h-series / g-series
Hide thumbs Also See for 2MXS40H2V1B:
Table of Contents

Advertisement

Field Settings
4.2

SA Indoor Unit - FFQ Series

4.2.1 How to Change the Field Settings
Outline
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
Wired remote
BRC1D528
controller
To set the field settings, you have to change:
231
Unit No.
Second
code No.
First
code No.
(4)
(3)
(1) (7)
Mode No.
First code No.
Second code No.
Step
Action
1
Press the [INSPECTION/TEST OPERATION] button for 4 seconds during normal
mode to enter the field setting mode.
2
Press the [TEMPERATURE ADJUST] button to select the desired mode No.
3
If the indoor unit is under group control, all settings for all the indoor units are
set at the same time. Use the codes 10 to 15 to apply this group control and
proceed to the next step.
If you want to set the indoor units of one group individually or if you want to
read out the last settings, use the codes 20 to 25 which are displayed in
brackets. Press the [PROGRAMMING] button to select the indoor unit No. for
which you want to adjust the field settings.
4
Press the upper part of the [TIME ADJUST] button to select the first code No.
5
Press the lower part of the [TIME ADJUST] button to select the second code No.
6
Press the [SCHEDULE TIMER] button to confirm the setting.
7
Press the [INSPECTION/TEST OPERATION] button to return to normal mode.
0-01
(6)
(5)
(2)
Trial Operation and Field Settings
SiBE121123_A
Mode No.
Field
setting
mode
(R14595)