Field Settings
4. Field Settings
4.1
RA Indoor Unit - FTXG, FTXS, ATXS, FTX, ATX, FVXG,
FVXS, FLXS, FDXS Series
4.1.1 Model Type Setting
ARC466A6, ARC466A9
ARC452A1, ARC452A3
225
This remote controller is common to the heat pump model and cooling only model.
The heating operation will not be available when the jumper on the left side is cut. Replace
the remote controller if you cut the jumper on the left side.
This remote controller is common to the heat pump model and cooling only model.
Make sure the DIP switch is set to the left side. The heating operation will not be available
when the DIP switch is set to the right side.
Never cut this jumper.
DIP switch
H/P
C/O
Trial Operation and Field Settings
SiBE121123_A
(R18451)
(R12755)