Step 3:- Radio Cluster Communicator (RCC) Installation and Programming

The RCC's should be installed installing in designated locations. Installation instructions
are supplied with each unit and should be followed.
A unique ident number is shown on the side of each RCC, this should be recorded as it is
required when adding the RCC to the Radio Hub.
From Front Display
Select Desired Loop & Device Address
'Enter the RCCs ident
* = If the RCC's signal path is to be direct to the Radio Hub then Radio Hub should be
selected. If the RCC's signal path is via another RCC, then the relevant RCC will need to
be selected. Each option can be chosen by turning the rotary switch.

Step 4:- Assigning the RCC'S

The newly added RCC's should now be assigned.
From Un-Assigned Dev
changing to Done 001 of 001 (once complete).

Step 5:- Allocate Device Radio Communication Channels

The Radio Channels used to communicate between the RCC's and the Devices are factory
set. It is recommended that they are re-configured to suit the sites environment. This
must be carried out before any devices are added to the system.
From Front Display
Are You Sure Y?
View Results Y/N?
Note: The longer the duration selected for the Scan Time then the more accurate the results will
be. Available times are between 1-60 minutes. For more information, see Radio Channels
within the Menu Structure section for more information.
Note: Having assigned the Radio Channels we must now re visit 'Step 4 – Assign RCCs' to re
assign the RCCs.
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
Technical Helpline Tel: +44 (0) 8712 710804
System Programming Manual (Rev2 iss4)
Hub/RCC Options
New Addr L1 A002.
Assign Device
Radio Channels
Scan Time 1min
To Exit
Email:
enquiries@emsgroup.co.uk
Add RCC
Select Desired Signal Path *
Add By Ident
Add Dev 12345 Y?
To Exit
Dev 000 of 001
To Exit
Device
RCC Ch
Decrementing Timer
Website:www.emsgroup.co.uk
Auto Select
All
Auto Ch 03 Ch 28