Start Fast Test

In this menu, loops can be entered into fast test for ease of testing. This allows the detectors on
the selected loops to be triggered into an alarm condition quicker than normal. The led on the
device will flash to indicate it is in this fast test mode.
minutes is selectable which decrements and is then re-generated on a fire alarm event.
devices automatically come out of fast test mode when the timer expires or the fast test mode is
exited.
Front Display
Advanced

RCC Comms Path

This menu allows you to view the path of communication between Radio Cluster Communicator
(RCC) to the Radio Hub whether it is direct from the RCC to the Radio Hub or from the RCC to the
Radio hub via another RCC.
number of hops the RCC uses to communicate to the Hub. Pressing the rotary control with the
required RCC shown will then show the RCC or Hub that particular RCC is communicating to.
Front Display
Advanced

Chg RCC Comms Path

This menu allows you to change the path of communication between Radio Cluster Communicator
(RCC) to the Radio Hub whether it is direct from the RCC to the Radio Hub or from the RCC to the
Radio Hub via an RCC.
Front Display
Advanced

Replace RCC

This menu allows you to replace the RCC with a new unit.
Front Display
Advanced
Sounder Mode
This menu allows the auto silencing of radio sounders to be programmed. Available options are
Continuous which disables any auto silencing rules and 30 min cut off. The default setting is to
30 min cut off which will turn all radio sounders off after 30 minutes to conserve battery life. Any
subsequent fire alarm activations will re-activate the sounders again.
Front Display
Advanced
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
Technical Helpline Tel: +44 (0) 8712 710804
System Programming Manual (Rev2 iss4)
Start Fast Test
The loop number and address number is shown along with the
RCC Comms Path
Chg RCC Comms Path
Replace RCC
Sounder Mode
Email:
A time period of between 1 and 30
enquiries@emsgroup.co.uk
Website:www.emsgroup.co.uk
The
32

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents