5.7 Advanced

Within this menu, a selection of advanced options are available.
Front Display
Advanced

Change Address

This menu allows the Loop number and address of a device to be changed if required.
Front Display
Advanced
Device
RCC Listing
This menu allows you to view all of the devices assigned to each RCC. Once the desired RCC has
been selected, devices can be viewed by scrolling through the list of devices.
Front Display
Advanced

Global Batt Stat

This menu allows the radio devices battery statuses to be viewed. The devices are listed in loop
and address order.
Each device will show the status of its two battery packs.
displayed as follows;
P1 and a full battery icon – this indicates a good battery voltage is present in Pack 1.
P1 and a half full battery icon – this indicates the battery voltage is low in Pack 1 and is a 30
day warning indication.
P1 and an empty battery icon – this indicates the battery voltage is low in Pack 1 and is a 7
day warning indication.
P1 and an X symbol – this indicates a battery from Pack 1 is missing.
P2 and a full battery icon – this indicates a good battery voltage is present in Pack 2.
P2 and a half full battery icon – this indicates the battery voltage is low in Pack 2 and is a 30
day warning indication.
P2 and an empty battery icon – this indicates the battery voltage is low in Pack 2 and is a 7
day warning indication.
P2 and an X symbol – this indicates a battery from Pack 2 is missing.
Front Display
Advanced

Global Sig Stat

This menu will display the signal level in dB's for each device and RCC over a 24 hour period.
This is listed in Loop and Address Number order. After the system has been running for a 24
hour period the device signal levels should display 30dB or above and the RCC signal levels
should displayed 20dB or above.
the flowchart On How to Improve Device Signal Levels section for guidance.
Front Display
Advanced

Individual Test

In this menu, output tests can be performed on individual devices. This will allow the LED's to be
turned on for detectors and callpoints, individual sounder operation and relay output operation on
Input /Output units.
Front Display
Advanced
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
Technical Helpline Tel: +44 (0) 8712 710804
System Programming Manual (Rev2 iss4)
Change Address
Device
RCC Listing
Global Batt Stat
If any devices are under the signal level requirements check
Global Sig Stat
Individual test