5.0 MENU EXPLANATION

5.1 Device Status

The device status menu lists all of the devices assigned to all the loops. Devices can be scrolled
through using the rotary controller. The allocated Loop and address numbers are shown along
with the device type and its current status.
number order.
Front Display
Device Status
A typical display is shown below;
The descriptions for the shown display are as follows;
L1 – In this example this indicates that the device is assigned to loop 1.
A003 - In this example this indicates that the device is assigned to address 003.
L - This field indicates the devices current status.
Available options are:
Optic – This field indicates the device type.
Available options are:
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
Technical Helpline Tel: +44 (0) 8712 710804
System Programming Manual (Rev2 iss4)
L1 A003 L Optic
L = Logged On to the RCC and in normal condition.
U = Device is unassigned to an RCC.
C = Combined sounder / detector logged on to the RCC and in normal
condition. Note: such device shall hold two loop addresses. (The first
for its sounder and the next for its detector).
! = Fault present. (See fault status descriptions).
= Fire present.
= Pre alarm present.
Optic = Optical Detector
Sound = Sounder Device
I/O = Input/Output Device
Multi = Multi-sensor Detector
Heat = Heat Detector
Ht Heat = High Temperature Detector
MCP = Manual Callpoint