I/0 Status

This shows the current Input and Output information on Input/Output devices.
status of the inputs and outputs for a particular device, the rotary control can be pushed to select
the device and this will then display the status information description.
Front Display
Device Status
The available descriptions are shown below;
IN: 0-0 – this indicates that input 1 and 2 is in the open (normal) state.
IN: 1-0 – this indicates that input 1 is in the closed (activated) state.
IN: 0-1 – this indicates that input 2 is in the closed (activated) state.
IN: 1-1 – this indicates that input 1 and 2 is in the closed (activated) state.
OUT: 0-0 – this indicates that output 1 and 2 is in the open (normal) state.
OUT: 1-0 – this indicates that output 1 is in the closed (activated) state.
OUT: 0-1 – this indicates that output 2 is in the closed (activated) state.
OUT: 1-1 – this indicates that output 1 and 2 is in the closed (activated) state.

Battery Level

This menu when entered shows information on the selected device's battery status. The status of
the pack is updated whenever there is a status change or automatically updated every 6 hours.
This is broken down into five sections.
Front Display
Device Status
Each device will show the status of its two battery packs.
displayed as follows;
Pack 1 OK – this indicates a good battery voltage is present in Pack 1.
displaying a full battery icon.
Pack 1 Warning – this indicates the battery voltage is low in Pack 1 and is a 30 day warning
indication.
The batteries must be changed on the device within 30 days for continued reliable
operation. This is represented by displaying a half full battery icon.
Pack 1 Low – this indicates the battery voltage is low in Pack 1 and is a 7 day warning
indication.
The batteries must be changed on the device within 7 days for continued reliable
operation. This is represented by displaying an empty battery icon.
Pack 1 Missing – this indicates a battery from Pack 1 is missing.
on the device for continued reliable operation. This is represented by displaying an X symbol.
Pack 2 OK – this indicates a good battery voltage is present in Pack 2.
displaying a full battery icon.
Pack 2 Warning – this indicates the battery voltage is low in Pack 2 and is a 30 day warning
indication.
The batteries must be changed on the device within 30 days for continued reliable
operation. This is represented by displaying a half full battery icon.
Pack 2 Low – this indicates the battery voltage is low in Pack 2 and is a 7 day warning
indication.
The batteries must be changed on the device within 7 days for continued reliable
operation. This is represented by displaying an empty battery icon.
Pack 2 Missing – this indicates a battery from Pack 2 is missing.
on the device for continued reliable operation. This is represented by displaying an X symbol.
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
Technical Helpline Tel: +44 (0) 8712 710804
System Programming Manual (Rev2 iss4)
Select Desired Device No
Select Desired Device No
Email:
enquiries@emsgroup.co.uk
IN: *-* OUT: *-*
Battery Level
The battery status information is
The battery must be inserted
The battery must be inserted
Website:www.emsgroup.co.uk
To view the
This is represented by
This is represented by
22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents