EMS FireCell FC-200-003 Installation Manual

Wireless manual call point (apollo front)

Advertisement

Quick Links

Wireless Manual Call Point (Apollo Front)
Installation Guide
REMOVE LABEL ON COMMISSIONING
1 Pre installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if
mounting the device on to a metal surface.
Do NOT Press the Log On button on a pre-programmed device,
as this will cause communication with the Control Panel to be
lost. Should this happen, delete the device from the system and
add it back on.
This device contains electronics that may be susceptible to
damage
from
Electrostatic
appropriate precautions when handling electronic boards.
3 Fix mounting plate
Remove the mounting plate from the wireless call point. See
Step 5 for more information on unlocking the device.
Ensure mounting plate is fitted in the orientation shown.
A minimum of 2 mounting holes
must be used.
Use suitable fasteners and fixings.
5 Device locking
To open the call point, loosen
the fixing screw, then slide
the call point up, away from
the
mounting plate.
When reassembling, observe
the
hinged
connection
located on the devices top
edge first, prior to closing the
unit. Finally lock the call point
into the mounting plate by
tightening the fixing screw.
©2021 EMS Ltd. All rights reserved
REMOVAL
RESET
Discharge
(ESD).
67 mm
57 mm
Fixing screw
Bottom view
of device
Part no
FC-200-003
2 Components
1
1
Reset key
Take
4
Wireless Call Point
4 Power device
When fitting / replacing batteries; observe correct polarity,
using only specified batteries.
Connect the power jumper across the PIN header.
Once powered, reassemble the device.
6 Configuration
The device's loop address is configured within the user interface's
menu structure.
Refer to the programming manual for full programming details.
FireCell = MK98
Fusion = TSD062
WZM = TSD143
Free to download from
www.emsgroup.co.uk
Page 1 of 2
Product description
Wireless Manual Call Point (Apollo Front)
2
3
2
Transparent cover
5
Mounting plate
device
unpowered
(pins unlinked)
device
powered
(both pins linked)
MK289-99 Iss 3 23/11/2021
4
5
3
Fixing screw
AJM

Advertisement

loading

Summary of Contents for EMS FireCell FC-200-003

  • Page 1 Finally lock the call point WZM = TSD143 into the mounting plate by tightening the fixing screw. Bottom view Free to download from of device www.emsgroup.co.uk ©2021 EMS Ltd. All rights reserved Page 1 of 2 MK289-99 Iss 3 23/11/2021...
  • Page 2 Part 25: Components using radio links. power Auto adjusting 0 to 14 dBm (0 to 25 mW) European Union EMS declares that this device is in compliance with Dimensions (W x H x D) 90 x 98 x 72.5 mm directives Directive 2014/53/EU.