ADEMCO Vista-15 Installation And Setup Manual page 86

Hide thumbs Also See for Vista-15:
Table of Contents

Advertisement

VISTA-15/VISTA-15CN Installation and Setup Guide
California State Fire Marshal (CSFM) 24-Hour Battery Back-Up
Requirements
The California State Fire Marshal has published new regulations which require that all residential
fire alarm control panels installed after June 30, 1993 must be provided with a back-up battery
which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in
the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling
condition.
This control panel can meet these requirements without using a supplementary power supply,
provided that the panel's auxiliary power and bell output currents are limited as indicated in the
following table.
OUTPUT LIMITATIONS TO MEET CSFM 24-HOUR BATTERY BACK-UP REQUIREMENTS
OUTPUT CURRENT LIMITATIONS
OUTPUT CURRENT
TOTAL
600mA maximum total
of
auxiliary power
plus bell output
currents.
‡ Note: Use two batteries, connected in parallel. Obtain an ADEMCO No. 4100EOLR Resistor Kit. A dual battery
harness is provided with the kit. The kit also contains EOL resistors with spade lug/heat shrink tubing
construction which has been approved by UL and CSFM for fire zone usage. Both batteries will fit inside
the panel's cabinet
B-2
FOR UL LISTED RESIDENTIAL FIRE INSTALLATIONS
MAXIMUM
AUXILIARY CURRENT
45mA
160mA
200mA
425mA
BATTERY INFORMATION
BATTERY CAPACITY
TO USE (Amp/Hrs)
4AH
7AH
8AH
14AH
RECOMMENDED BATTERY
(Yuasa Model No.)
NP4-12
NP7-12
NP4-12 (two) ‡
NP7-12 (two) ‡