FIELD
TITLE and DATA ENTRIES
Cross Zone Timer (in seconds)
*85
0 = 30; 1 = 45; 2 = 60; 3 = 90; 4 = 120; 5 = 180;
6 = 240
Alarm Pager Delay Time
*87
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3
minutes
Pager Characters
*88
Event Log 80% Full Report Code
*89
Event Logging
*90
0 = no event logging
1 = log Alarm/Alarm Restore
2 = log Trouble/Trouble Restore
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of events (add value of entries)
Example: To select "Alarm/Alarm Restore" and
"Open/Close," enter 9 (1 key + 8 key); to select all
events, enter #15.
The default of 3 = Alarm/Alarm Restore (1) plus
Trouble/Trouble Restore (2).
EXPLANATION
Sets the maximum amount of time in which two cross zones (zone list 04)
must be tripped in an armed system to send an Alarm message to the
Central Station. If only one cross zone is tripped during this time, a
Trouble message (report) is sent to the Central Station.
This option not for use in UL installations.
This field determines the delay of alarm reports to the pager. This gives
the Central Station enough time to verify the alarm report that it received,
before the dialer is tied up trying to dial the pager.
When programmed in field ✱ 47, reports are sent to the pager depending
upon the number selected.
This programming field ( ✱ 88) allows up to 16 digits to be entered to
signal a pager. For example, These optional 16 digits may be composed
of the following:
PIN number (to identify a specific pager to the paging company)
subscriber account number
✱ (enter # + 11 to send ✱)
# (enter # + 12 to send #)
pause (enter # + 13 to allow a 2-second pause)
any special character(s) the end user may decide to transmit
All 16 digits do not have to be used.
The preceding 16 digits (if any) are followed by a 7-digit Pager Format,
which is defined as follows:
Pager Format: XXX-YYYY
where:
XXX=a 3-digit event code:
911 = Alarm101 = Opening (disarm)
811 = Trouble102 = Closing (arm AWAY)
YYYY=user or zone number (depending on type of event)
The first two digits must always be 00, and must be followed by the 2-
digit user or zone number. Paging is enabled in the Split/Dual Reporting
field ✱ 47 by entering a number greater than 5.
NOTE: Some pagers may require an additional delay (pause) to be
programmed into this field in order to receive the entire message. Field
✱ 87 provides an optional pager reporting delay of 0, 1, 2, or 3 minutes for
alarm messages only. Enter # + 13 for a 2-second pause.
If an Event Logging selection is made in field ✱ 90, a message can be
sent to the Central Station receiver when the log is 80% full. If the log
becomes full, a new message overwrites the oldest message in the log.
NOTE: Aside from the selection made by the installer in field ✱ 90, all
control and readout from the log is accomplished via the downloader.
The VISTA-15/VISTA-15CN system can record up to 48 events in a
history log. The types of events to be logged are selectable. At any time,
the downloader operator can then upload the log and view or print out all
or selected categories of the log. The downloader operator can also clear
the log.
The display/printout at the Central Station shows the date, time, event,
and description of the occurrences. The time is calculated by an internal
clock in the panel. Note that the time for any events that occur prior to a
system power-down or an entry into the Programming mode cannot be
calculated by the panel. The time then appears on the log as "unknown."
NOTE: System messages are logged when any nonzero selection is
made.
Section 5 - Data Field Programming
5–9