9.0 Overheat Cut-off Device

9.1
Operation
1. The overheat cut-off device is of the manual
reset type and therefore it is important that the
user knows how to reset the control should it
ever operate.
NOTE: Cut-off is indicated by illumination of
the overheat neon light on the control box.
2. Hinge the lower door panel down (Fig 89).
3. To reset the boiler - Turn the boiler
thermostat control knob fully anti-clockwise to the
OFF position marked '0' (Fig. 90). Wait ten
seconds, then turn the control knob clockwise to
the required thermostat setting. The red neon will
go out and the boiler will start automatically.
Fig. 89
4. If the overheat cut-off operates repeatedly,
refer to the fault finding chart at the rear of this
booklet and investigate the cause.