Baxi Solo 3 Installation And Servicing Instructions page 20

Baxi solo 3 pfl system, wall mounted powered flue system boiler, gas fired central heating unit
Table of Contents

Advertisement

Maximum lengths for side flue using the standard telescopic flue kit
355mm
Fig. 31
Fig. 32
Fig. 33
20
Supplied By www.heating spares.co Tel. 0161 620 6677
335mm
Fig. 34
Fig. 35
Fig. 36
6.0 Installation
6.7
Left or Right Flue
NOTE: If the flue terminal is inaccessible from
outside the building, it is necessary to fix the
internal fitting kit in position before continuing
with the installation. (See section 5.15 Internal
Fitting Kit of these instructions).
1. The procedure for fitting the appliance flued to
the left or right hand side is the same.
2. Left Hand Side maximum flue 355mm.
3. Right Hand Side maximum flue 335mm.
4. Optional flue extensions are available.
5. Using the previously marked flue hole centre,
mark the horizontal centre line for the flue
assembly (Fig. 31).
6. Extend this line either left or right as required,
to the corner of the room (Fig. 31).
7. Extend the horizontal centre line around the
corner for approximately 300mm (12 in). Ensure
that the line remains horizontal by checking with a
spirit level (Fig. 32).
8. From the wall template cut out the 'D' shaped
section. Line up the horizontal triangular cut outs
with the extended 300mm (12 in) line and make
sure that the flat of the template is butted up
against the corner of the wall (Fig. 33).
9. If the appliance mounting wall is out of true, use
string or a straight edge to determine the true
corner position and mark a vertical line to
accommodate the flat edge of the template.
10. Holding the template firmly, mark the vertical
centre line for the flue assembly by marking the
point at the outer corners of the upper and lower
cut outs (Fig. 34).
11. Remove the template and draw a vertical line
between the two marks. The intersection of the
vertical and horizontal lines is the centre of the
flue hole (Fig. 35).
12. For installations where the flue terminal is
inaccessible from the outside, an internal fitting kit
is available. This can be obtained free of charge
from your local merchant.
13. If using the internal fitting kit a 117mm (4
diameter hole is required.
14. Cut a hole approximately 107mm (4
diameter in the masonry for the 100mm (4 in)
diameter flue duct (Fig. 36). (Use of a core drill is
recommended. When using a core drill, it is
important to keep the drill level and square,
particularly with the wall onto which the boiler is to
be fitted).