Site Requirements - Baxi Solo 3 Installation And Servicing Instructions

Baxi solo 3 pfl system, wall mounted powered flue system boiler, gas fired central heating unit
Table of Contents

Advertisement

L
K
G
D
J
Likely flue positions requiring
a flue terminal guard
Horizontal Terminal Position with Minimum Distance
A
Directly below an openable window, air vent or any other
ventilation opening.
B
Below gutter, drain/soil pipe.
C Below eaves.
D Below a balcony/car port roof.
E
From vertical drain pipes and soil pipes.
F
From internal or external corners.
G Above adjacent ground or balcony level.
H From a surface or boundary facing a terminal.
I
Facing a terminal.
J
From opening (door/window) in carport into dwelling.
K
Vertically from a terminal on the same wall.
L
Horizontally from a terminal on the same wall.
M Above an opening, air brick, opening window etc.
N Horizontally to an opening, air brick, opening window etc.
Table. 2
NOTE: Scotland Only - The distance from a fanned draught appliance
terminal installed at right angles to a boundary may not be less than
300mm in accordance with the diagram below.
Terminal
Assembly
Top View Rear Flue
Maximum lengths for side flue using the standard telescopic flue kit
355mm
12
Supplied By www.heating spares.co Tel. 0161 620 6677
B,C
N
G
M
D
H,I
A
A
E
F
F
G
Fig. 10
300 min
Property Boundary Line
335mm
Fig. 11

5.0 Site Requirements

5.3
Flue Position (Cont)
WARNING - The addition of anything that may
interfere with the normal operation of the
appliance (e.g. FLUE DAMPERS,
ECONOMISERS,etc.) without the express
written permission of Baxi UK Limited could
invalidate the appliance warranty and infringe
the GAS SAFETY (Installation and Use)
REGULATIONS.
If a terminal is less than 2 metres (78
above a balcony, above ground or above a flat
roof to which people have access then a
(mm)
suitable terminal guard must be provided.
300
6. The flue terminal position must always be
150
in accordance with the current edition of B.S.
200
200
5440 Part 1, and either Part J of the Building
150
Regulations England and Wales or Part F of
300
the Building Standards (Scotland)
300
Regulations as appropriate.
600
1200
7. Table 2 and Fig. 10 show the positioning of the
1200
flue terminal relative to buildings and other
1500
300
structures.
300
300
8. The dimensions of the flue terminal are shown
in Section 3.0 Technical Data.
5.4
Flue Dimensions
1. Flue extensions are available as optional
extras for installations up to 3 metres
horizontal.
2. Vertical flue kits are available up to 4
metres in length. Vertical twin flue kits are
available up to 15 metres in length.
3. The standard telescopic flue is suitable for use
with rear flue lengths between 100mm (4in) and
500mm (19
5
/
in).
8
4. Where it is intended to pass the flue through a
combustible wall or timber framed dwelling,
reference should be made to the Institute of Gas
Engineers document UP7 - Guide for Gas
Installations in Timber Framed Dwellings.
5. If the flue is more than 1 metre (39
is required that it is supported.
6. All above dimensions are taken from the
respective faces of the outer case.
3
/
in)
4
3
/
in) long, it
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents