Installation
AC Input Power Connection
3. Slide the helix-shaped body onto the AC cable. Insert the stripped wires through
the strain relief base until the outer cable jacket is flush with the edge of the base.
Tighten the body to the base while holding the cable in place. The cable is now
securely fastened inside the strain relief.
4. Route the AC wires to the input connector terminals as required. For input
connector terminal locations, see lower inset in Figure 2.2. To connect the
wiring, loosen the terminal screw, insert the stripped wire into the terminal, and
tighten the screw securely.
5. Route the wires inside the cover to prevent pinching. Fasten the AC input cover
to the unit using the 6-32 x 1 1/4 in. (2) screws, flat washers, and lock washers
provided. See Figure 2.2.
Assembled
Strain Relief
Flat Washer (2 places)
Lock Washer (2 places)
Screw (2 places)

Figure 2.2 AC Input Cover and Strain Relief

42
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Cover
Stripped Wire Installed in Strain Relief
Operating Manual for XFR 1.2kW Series Power Supply
Screw-on
Locknut
Connector Terminal Locations