14. Firmware update

This section explains the procedure for updating the firmware of the unit.

14.1. Update process

To load firmware to the unit the memory card must be SD HC (High Capacity).
1.
Check the version of firmware installed in the inverter using the display, accessing Main menu > Inverter
data > FW version.
2.
The firmware is updated using a SD HC type memory card (not supplied by Ingeteam). There must be a
card of this type in FAT32 format. The card must be formatted and must not contain any files.
3.
To download the latest firmware available go to the Ingeteam website (www.ingeteam.com). On the
website, access Energy > PV energy > INGECON SUN 1Play and go to the Downloads area. Here you will find
the .rar or .zip file containing the files necessary to load the firmware.
The name of the file shall be of the type XXXXXXXXX_z, where _z indicates the version of the file. The first
version will be _ and will continue with _A, _B, etc.
4.
Extract the two files included in the file you have downloaded to the root directory of the memory card.
5.
With the inverter running, open the cover of the card reader and insert the SD card.
6.
In a few seconds the inverter automatically recognises the firmware and starts the update process. The
inverter disconnects from the grid causing a reason for shutdown due to firmware update.
7.
A message will be displayed on screen confirming that the firmware is being loaded. Do not remove the
memory card.
8.
The main menu will be displayed once the firmware has been loaded. At that moment you can remove the
SD card by pressing it gently.
9.
To maintain the protection rating of the unit after this task you must always replace the cover over the
card reader.
38
ABF2011IQE01_A - Installation and usage manual
Firmware update