Tables Of Specifications; General Data - Ingeteam Ingecon Sun 1Play HF Installation And Usage Manual

Hide thumbs Also See for Ingecon Sun 1Play HF:
Table of Contents

Advertisement

Ingeteam

2.8. Tables of specifications

DC input
Recommended power range of PV array
Maximum input voltage
(2)
MPP voltage range
Operating voltage range
Minimum voltage for Pnom
Maximum short circuit current
Maximum inverter backfeed current to the
array
MPPT
Number of strings
Strings per MPP
Maximum input current
Maximum input current per string
AC output
Nominal power (up to 45 ºC)
Maximum continuous power
Max. temperature for nominal power
Maximum current
Maximum transient current
Maximum output fault current
Maximum output overcurrent protection
Rated voltage
Voltage range
Nominal frequency
Cosine of Phi
Adjustable cosine of phi
THD
Performance
Maximum efficiency
Euroefficiency

General data

Cooling system
Air flow
Weight
Measurements (height x width x depth)
Stand-by current
(4)
Nocturnal current
Operating temperature
Relative humidity (without condensation)
Protection rating
Markings
EMC and safety regulations
Grid connection regulations
Depending on the type of installation and geographical location.
(1)
temperatures.
(3)
For each ºC of increase, the output power is reduced by 1.8 %.
10
2.5HF
2.8 ~ 3.3 kWp
(1)
550 V
125 ~ 500 V
125 ~ 550 V
147 V
19 A
0 A rms
1
2
2
17 A
17 A
2.5 kW
2.5 kW
51 ºC
(3)
13.5 A
13.5 A
< 16 A rms (60 ms)
16 A rms
230 V
122 ~ 285 V
50 / 60 Hz
1
Yes. Smax = 2.5
Yes. Smax = 2.7
kVA
< 3 %
95.6 %
95 %
Natural convection
-
20 kg
< 10 W
0 W
–25 ~ +65 ºC
0 ~ 100 %
IP65
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-11, EN 61000-3-12, EN
62109-1, EN 62109-2, IEC62103, EN 50178, FCC Part 15, AS3100
RD1699/2011, DIN V VDE V 0126-1-1, EN 50438, CEI 0-21, VDE-AR-N 4105:2011-08, G59/2,
G83/2, P.O.12.3, AS4777.2, AS4777.3, IEC 62116, IEC 61727, UNE 206007-1, ABNT NBR 16149,
ABNT NBR 16150, South African Grid code, Chilean Grid Code, Romanian Grid Code, Ecuadorian
Grid Code, Peruvian Grid code, IEEE 929, Thailand MEA & PEA requirements
Never exceed this value. Consider the voltage increase of the panels 'Voc' at low
(2)
2.7HF
3HF
3 ~ 3.6 kWp
3.2 ~ 4 kWp
550 V
550 V
125 ~ 500 V
125 ~ 500 V
125 ~ 550 V
125 ~ 550 V
159 V
142 V
19 A
25 A
0 A rms
0 A rms
1
1
2
2
2
2
17 A
22 A
17 A
17 A
2.7 kW
3 kW
2.7 kW
3 kW
48 ºC
55 ºC
13.5 A
16 A
13.5 A
16 A
16 A rms
18 A rms
230 V
230 V
122 ~ 285 V
122 ~ 285 V
50 / 60 Hz
50 / 60 Hz
1
1
Yes. Smax = 3
kVA
kVA
< 3 %
< 3 %
95.6 %
95.8 %
95.1 %
95.2 %
-
45 m
/h
3
20 kg
22 kg
470 x 360 x 180 mm
< 10 W
< 10 W
0 W
0 W
–25 ~ +65 ºC
–25 ~ +65 ºC
0 ~ 100 %
0 ~ 100 %
IP65
IP65
CE
(4)
Current from PV array.
ABF2011IQE01_A - Installation and usage manual
Unit description
3.3HF
3.68HF
3.8 ~ 4.3 kWp
3.9 ~ 4.8 kWp
550 V
550 V
125 ~ 500 V
125 ~ 500 V
125 ~ 550 V
125 ~ 550 V
150 V
167 V
25 A
25 A
0 A rms
0 A rms
1
1
2
2
2
2
22 A
22 A
17 A
17 A
3.3 kW
3.68 kW
3.3 kW
3.68 kW
52 ºC
50 ºC
16 A
16 A
16 A
16 A
< 18 A rms (60 ms)
18 A rms
18 A rms
230 V
230 V
122 ~ 285 V
122 ~ 285 V
50 / 60 Hz
50 / 60 Hz
1
1
Yes. Smax = 3.3
Yes. Smax = 3.68
kVA
kVA
< 3 %
< 3 %
95.8 %
95.8 %
95.2 %
95.1 %
Forced ventilation
45 m
/h
45 m
/h
3
3
22 kg
22 kg
< 10 W
< 10 W
0 W
0 W
–25 ~ +65 ºC
–25 ~ +65 ºC
0 ~ 100 %
0 ~ 100 %
IP65
IP65

Advertisement

Table of Contents
loading