Shutting Down The Unit; Process Of Shutting Down The Unit - Ingeteam Ingecon Sun 1Play HF Installation And Usage Manual

Hide thumbs Also See for Ingecon Sun 1Play HF:
Table of Contents

Advertisement

Ingeteam

16. Shutting down the unit

This section describes the procedure to shut down the unit. If you wish to work inside the unit, these instructions
must be carried out in the order shown here to remove the power.

16.1. Process of shutting down the unit

1.
Proceed to stop mode from the inverter display.
2.
Disconnect the client Vac and Vdc voltage.
3.
Wait 10 minutes for the internal capacitances to discharge, the hot parts which may cause burns to cool
and the .fan blades to stop turning.
4.
Check there is no voltage.
5.
Signal cut-off point (Vac and Vdc) with a sign reading ¨Caution no switching...¨. If necessary, rope off the
work area.
40
Shutting down the unit
ABF2011IQE01_A - Installation and usage manual

Advertisement

Table of Contents
loading

Table of Contents