Engineering conditions of acceptability by Underwriters Labaratories Inc. (UL) ..5.2.3 Requirements for the mounting position ..............Cable preparation......................5.3.1 Overview of interfaces....................5.3.2 Preparation of cables with D-Sub connector............... 5.3.3 Power supply....................... 5.3.4 RS232 (System Port) ....................MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 4
9.1.6 15" devices with 4-hole front ..................Display ........................Touch sensor ......................9.3.1 Devices with resistive touch ..................9.3.2 Devices with infra-red touch..................System ........................Interfaces ........................9.5.1 Power supply....................... Enclosure ratings ......................MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 5
Contents Agency approvals and standards................Applicable standards and regulations ................. Ambient conditions...................... MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Additional documentation The following documents may be helpful in the use of the device in addition to this document. These can be downloaded from our home page (www.eaton-automation.com/en), «DOWNLOADS» section. [1] MN05010007Z-EN System Description Windows CE (operation of the Windows CE operating system on MICRO PANELs)
XV-440-12TSB-1-2x MC2-440-12TSB-1-2x Infra-red touch 12.1", stainless steel front XV-440-12TSB-1-5x MC2-440-12TSB-1-5x Infra-red touch 15", standard front XV-460-15TXB-1-1x Infra-red touch 15", 4-hole front XV-460-15TXB-1-2x Infra-red touch 15", stainless steel front XV-460-15TXB-1-5x Tab. 1 Device versions MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 10
Fig. 1 XV400, MC2 with resistive touch and standard front Fig. 2 XV400, MC2 with infra-red touch and standard front Fig. 3 XV400, MC2 with infra-red touch and 4-hole front Fig. 4 XV400, MC2 with infra-red touch and stainless steel front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Retaining brackets with threaded pin for mounting the device Sealing strip for mounting the device Power supply connector CF slot cover (fitted) Slot covers (fitted) Tab. 3 Package contents for 10.4" and 12.1" devices with infra-red touch and standard front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
XV-460-15TXB-1-2x Countersunk screws for mounting the device Front seal for mounting the device Power supply connector CF slot cover (fitted) Slot covers (fitted) Tab. 5 Package contents for devices with 4-hole front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Arrangement of interfaces and operating elements Support To ensure fast and optimum support always provide the support personnel with the following informa- tion on the nameplate: Part no. (Part-No or Art.-No) Serial no. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Read this chapter before working with the device. This contains important information for your personal safety. This chapter must be read and understood by all persons work- ing with this device. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Signal word CAUTION without safety alert symbol Indicates a situation which, if not avoided, could result in material damage. Indicates useful information. The danger symbol used and the text indicate the actual danger and the related preventative measures. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
It must be ensured that the device is properly connected, mounted, maintained and disposed of in compliance with all relevant standards and safety regulations. 3.3.5 Prohibited use The implementation of safety functions (relating to the protection of personnel and machinery) using the device is prohibited. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Failure or malfunction of the device Improper handling or use Failure to observe the Operating Instructions Conversions, modifications and repairs to the device Repairs, see Chapter 7.3.1 Repairs, 62. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Avoid contact with components (such as connector pins) that are susceptible to electrostatic discharge. Discharge (by touching a grounded metal object) any static charge accumulated in your body before touching the device. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 20
Do not use any pointed or sharp objects (e.g. knife) for cleaning. Do not use any aggressive or abrasive cleaning agent or solvent. Avoid any liquid entering the device (risk of short-circuit). MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
(min. ø 7 mm). It is not necessary to touch the infra-red touch protective panel. B Display Display operating and indication elements. Tab. 7 Operating and indication elements on the front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Slot for CF card with operating system and normally with PLC and visu- alization projects. D Ejector button Ejecting the CF card. E Control button Function depends on the software used. Tab. 8 Operating elements on the service side MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Flashes if the resistive touch is incorrectly calibrated (touch calibra- tion, → Document «MN05010007Z-EN System Description Windows CE»). E SUPPLY OK (green) Lit if all internal system voltages are present. Tab. 9 Indication elements on the service side MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 24
4 Operating and indication elements 4.3 Indication elements on the service side MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
5 Installation 5.1 Safety regulations Installation Safety regulations Read Chapter 3 Safety regulations, 15 before installing and commissioning the de- vice. This contains important information for your personal safety. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
The ambient conditions stated must be observed. See Chapter 9.9 Ambient conditions, 79. Sufficient ventilation (cooling) must be ensured by means of: Clearance of at least 3 cm to the ventilation slots MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 27
Material thickness at the mounting cutout 2…5 mm (devices with 4-hole front: 2…20 mm) Flatness ≤ 0.5 mm (this requirement must also be fulfilled when the device is mounted!) Surface roughness Rz ≤ 120 MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
The cables used must be prepared according to the interface description in this document. The wiring instructions for the relevant interface must be observed when wiring the device. Any generally applicable regulations and standards must be fulfilled. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
E USB Host 0 → Chapter 5.3.7, 35 F USB Host 1 → Chapter 5.3.7, 35 G CAN → Chapter 5.3.8, 36 H DIAG Only for service tasks Tab. 10 Overview of interfaces MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
The folded back shield braid end must be covered by the heat shrinkable tubing or by the rubber grommet. Fit the D-Sub connector to the cable end: The exposed metal shield braid must be clamped to the connector casing with the cable clamp. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 31
E D-Sub connector C Cable clamp F Mounting screw UNC The EMC values stated in the technical data (immunity and emission) can only be guar- anteed by observing the prescribed cable preparation! MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Pluggable screw terminal Cross-section min. 0.75 mm / max. 2.5 mm (lead or wire) min. AWG18 / max. AWG12 Stripping length 7 mm Tab. 12 Preparing the wiring of the connector MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Tab. 14 Relationship of cable length / baud rate When preparing the cables, ensure that there is a low-resistance connection between the cable shield and the connector casing (→ Chapter 5.3.2, 30). MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Communication can be disturbed and the connection mechanics damaged if the Ethernet interface is exposed to severe vibration or the RJ45 plug connection is pulled. Protect the RJ45 connection from severe vibration. Protect the RJ45 connection from pulling on the socket. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
5.3.7 USB Host The USB Host interfaces support USB 2.0. Fig. 18 USB Host interface (USB Host, type A) Cable Only use shielded USB standard cable. Maximum cable length: 5 m. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Capacitance per unit length < 60 pF/m ≥ 0.25 mm Core cross-section / max. cable length / 100 m ≥ 0.34 mm / 250 m ≥ 0.75 mm / 500 m Tab. 17 Cable specifications MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 37
No more than two terminations must be provided on each bus segment. Transmission faults can occur if operation is carried out without the correct termina- tion. Fig. 20 Bus segment with four bus stations MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
The device is not provided with an On/Off switch. If the power supply is not provided with a switch, the device will start up (boot) as soon as it is connected to the power sup- ply. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Avoid contact with components (such as connector pins) that are susceptible to electrostatic discharge. Discharge (by touching a grounded metal object) any static charge accumulated in your body before touching the device. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 40
Fit the communication module in the slot. Fasten the communication module with the two knurled screws. Refer to the relevant module description for information on protocol, configuration, cable lengths etc. of the communication module to be used. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Material thickness at the mounting cutout 2…5 mm 329.0 344.0 +1/-1 +1/-1 Fig. 22 Mounting cutout for 10.4" devices Fig. 23 Mounting cutout for 12.1" devices 410.0 +1/-1 Fig. 24 Mounting cutout for 15" devices MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 42
Fig. 25 Groove for sealing strip (A) Fit the supplied threaded pins in the retaining brackets beforehand. Fig. 26 Threaded pin pre-fitted in a retaining bracket Fit the device from the front into the mounting cutout. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 43
Top and bottom of the device: Fit one retaining bracket each at the left and right fixing position Fig. 27 10.4" and 12.1" devices with four retaining brackets (do not meet IP65 requirements) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 44
One retaining bracket each at the second fixing position from the left and from the right Left and right on the device: One retaining bracket each at the top and bottom fixing position Fig. 29 15" devices with eight retaining brackets (do not meet IP65 requirements) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 45
One retaining bracket each at the outermost and at the two innermost fixing positions Left and right on the device: One retaining bracket each at the two innermost fixing positions Fig. 30 15" devices with twelve retaining brackets (meet IP65 requirements) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
15" devices: From 430 mm (±0.2 mm) to 290 mm (±0.2 mm) Material thickness at the mounting cutout 2…20 mm 344.0 314.0 +1/-1 +1/-1 326.0 360.0 +0.2/-0.2 +0.2/-0.2 Fig. 31 Mounting cutout for 10.4" devices Fig. 32 Mounting cutout for 12.1" devices MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 47
CAUTION Poor sealing Poor sealing resulting from inaccurately positioned front seal. Ensure that the front seal is flat and fitted evenly between the front plate of the device and the mounting surface. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 48
Use the supplied countersunk screws and optional counter frame if: Mounting is required to comply with IP65, or The device is used in a potentially explosive atmosphere. Fig. 35 Counter frame (for mounting to IP65) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
15" devices: 410 × 315 mm (±1 mm) Material thickness at the mounting cutout 2…5 mm 329.0 344.0 +1/-1 +1/-1 Fig. 36 Mounting cutout for 10.4" devices Fig. 37 Mounting cutout for 12.1" devices MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 50
Do not twist the sealing strip when it is inserted. Cut the sealing strip to a suitable length so that the join is tight. Fig. 39 Groove for sealing strip (A) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 51
Top and bottom of the device: Fit one retaining bracket each at the left and right fixing position Fig. 41 10.4" and 12.1" devices with four retaining brackets (do not meet IP65 requirements) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 52
One retaining bracket each at the second fixing position from the left and from the right Left and right on the device: One retaining bracket each at the top and bottom fixing position Fig. 43 15" devices with eight retaining brackets (do not meet IP65 requirements) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 53
One retaining bracket each at the outermost and at the two innermost fixing positions Left and right on the device: One retaining bracket each at the two innermost fixing positions Fig. 44 15" devices with twelve retaining brackets (meet IP65 requirements) MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
If condensation is present on the device, or if it was exposed to temperature fluc- tuations, it must be allowed to adjust to room temperature (do not expose the de- vice to the direct heat of heating devices) prior to commissioning. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
CF card with data in CF slot 1 (B) Do not apply any force (CF cards are protected against reverse insertion). Fig. 46 Service side of the device (CF slot cover removed) Fit the CF slot cover (A). MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 57
System Description Windows CE»): Adjust the system settings of the device. Install the required application programs. The lifespan of the backlight can be increased by reducing the brightness (→ Document «MN05010007Z-EN System Description Windows CE»). MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
(CCFL) of the backlight. Avoid frequent on/off switching of the device. Reduce the brightness of the backlight instead (→ Document «MN05010007Z-EN System Description Windows CE»). De-energize the device. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
7 Maintenance and service 7.1 Safety regulations Maintenance and service Safety regulations Read Chapter 3 Safety regulations, 15 before working with the device. This contains important information for your personal safety. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Recalibrating a resistive touch The resistive touch is already calibrated when delivered. However, it must be recalibrated if it does not respond correctly to touch operation. Touch calibration, see Document «MN05010007Z-EN System Description Windows CE». MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
With stubborn contamination, spray a little cleaning agent onto the damp cloth first. 7.2.4 Recalibrating the infra-red touch Devices with infra-red touch do not have to be recalibrated. 7.2.5 Battery The integrated battery cannot be exchanged. Lifespan, see Chapter 9.4 System, 74. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Repairs The device must only be opened by the manufacturer or by an authorized repair center. Contact your local supplier or Eaton technical support for repairs. Only the original packaging should be used for transporting the device. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Start (boot) the device. Calibrate touch (→ Document «MN05010007Z-EN System Description Windows CE»). Infra-red frame of the infra-red touch is contam- Clean the infra-red frame inated. (→ Chapter 7.2.3, 61). MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Page 64
The threaded pins for mounting the device have Loosen the threaded pins (observe max. torque, → Chapter 5.4, 38). been tightened too much. Device is faulty. Send in your device for repair. Tab. 19 Troubleshooting MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Damage to the device must be prevented during transport (use an appropriate packaging). The ambient conditions must be fulfilled even when the device is transported. See Chapter 9.9 Ambient conditions, 79. Check the device on arrival for damage in transit. MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
329 mm × 238 mm (±1 mm) Weight Devices with standard front Approx. 4.1 kg Devices with stainless steel front Approx. 5.3 kg Tab. 22 Dimensions and weights of the 10.4" devices with standard or stainless steel front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Thickness of front plate 5 mm Mounting depth 88 mm 314 mm × 238 mm (±1 mm) Mounting cutout Weight Approx. 4.1 kg Tab. 23 Dimensions and weights of the 10.4" devices with 4-hole front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
344 mm × 262 mm (±1 mm) Weight Devices with standard front Approx. 4.5 kg Devices with stainless steel front Approx. 5.7 kg Tab. 24 Dimensions and weights of the 12.1" devices with standard or stainless steel front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Thickness of front plate 5 mm Mounting depth 88 mm Mounting cutout 344 mm × 262 mm (±1 mm) Weight Approx. 4.5 kg Tab. 25 Dimensions and weights of the 12.1" devices with 4-hole front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Mounting cutout Weight Devices with standard front Approx. 6.2 kg Devices with stainless steel front Approx. 7.5 kg Tab. 26 Dimensions and weights of the 15" devices with standard or stainless steel front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Thickness of front plate 5 mm Mounting depth 94 mm Mounting cutout 410 mm × 315 mm (±1 mm) Weight Approx. 6.2 kg Tab. 27 Dimensions and weights of the 15" devices with 4-hole front MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
2× CompactFlash Card Type I/II for operating system, programs and data Real-time clock (battery backup) Battery type CR2032 (190 mA/h), maintenance-free (soldered) Backup time in de-energized state Normally 10 years Tab. 31 System MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
Max. 32 W 15" devices Basic device Max. 30 W (normally 28 W) Communication module 2 × max. 4 W USB stations on USB host 2 × max. 3 W Total Max. 44 W MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
II 3D Ex II T70°C IP5x (ATEX 94/9/EC): Zone 22, category 3D: Required accessories for mounting: - Additional set of retaining brackets (optional) UL 60950: File no. E208621 Tab. 35 Agency approvals and standards MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
(Engineering conditions of acceptability by UL, → Chapter 5.2.2, 26) Product standards EN 50178 Electronic equipment for use in power installations EN 61131-2 Programmable logic controllers, equipment require- ments and tests Tab. 36 Applicable standards and regulations MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...
0 … 50°C Storage / Transport -20 … 60°C Relative air humidity 10 … 95%, non-condensing Vibration According to IEC68-2-6 Shock According to IEC68-2-27 Fall test According to IEC68-2-32 Tab. 37 Ambient conditions MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com...