Clearance of at least 15 cm from heat radiating components such as heavily loaded trans-
formers
The expected temperatures should be within the permissible range. See Chapter 9.9 Ambient
conditions, 79.
Properties of the mounting surfaces:
Material thickness at the mounting cutout 2...5 mm (devices with 4-hole front: 2...20 mm)
Flatness ≤ 0.5 mm
(this requirement must also be fulfilled when the device is mounted!)
Surface roughness Rz ≤ 120
MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com
5.2 Requirements for the place of installation
5 Installation
27