Mounting A Device With Standard Front - Eaton XV400 10.4" Operating Instructions Manual

Micro panel
Table of Contents

Advertisement

5.4.2

Mounting a device with standard front

An additional set of retaining brackets is required for mounting in accordance with
IP65 and for use in potentially explosive atmospheres. Please contact your supplier.
10.4" and 12.1" devices can be mounted horizontally or vertically, 15" devices must
only be mounted horizontally.
1
Select the mounting position of the device as described in Chapter 5.2.3 Requirements for the
mounting position,  26.
2
Prepare a mounting cutout for the device at the selected position:
Mounting cutout:
10.4" devices: 329 × 238 mm (±1 mm)
12.1" devices: 344 × 262 mm (±1 mm)
15" devices: 410 × 315 mm (±1 mm)
Material thickness at the mounting cutout 2...5 mm
329.0
+1/-1
Fig. 22 Mounting cutout for 10.4" devices
410.0
+1/-1
Fig. 24 Mounting cutout for 15" devices
MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com
344.0
+1/-1
Fig. 23 Mounting cutout for 12.1" devices
5 Installation
5.4 Mounting
41