CAN bus topology
The maximum baud rate depends on the cable length:
Cable length
25 m
50 m
100 m
250 m
500 m
500 m
1000 m
2500 m
5000 m
Tab. 18 Relationship of cable length / baud rate
The use of repeaters is recommended with cables over 1000 m in length. Repeaters
can also be used to implement electrical isolation. Refer to the documentation of the
repeater manufacturer for further information.
Observe the recommendations of the CiA (CAN in Automation).
When preparing the cables, ensure that there is a low-resistance connection between
the cable shield and the connector casing (→ Chapter 5.3.2,  30).
A bus segment can connect up to 32 bus stations.
Several bus segments can be linked via repeaters (bidirectional amplifiers). Refer to the documen-
tation of the repeater manufacturer for further information.
A bus segment must be provided with cable termination (120 Ω) at both ends. These terminations
must be connected in the connector, directly between pin 2 and 7.
The bus segment must be terminated at both ends.
No more than two terminations must be provided on each bus segment.
Transmission faults can occur if operation is carried out without the correct termina-
tion.
Fig. 20 Bus segment with four bus stations
MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com
5.3 Cable preparation
Max. baud rate
1000 Kbit/s
800 Kbit/s
500 Kbit/s
250 Kbit/s
125 Kbit/s
100 Kbit/s (adjustable via software)
50 Kbit/s
20 Kbit/s
10 Kbit/s
5 Installation
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xv400 12.1"Xv400 15"

Table of Contents