Mounting A Device With Stainless Steel Front - Eaton XV400 10.4" Operating Instructions Manual

Micro panel
Table of Contents

Advertisement

5.4.4

Mounting a device with stainless steel front

10.4" and 12.1" devices with a stainless steel front:
can be mounted horizontally or vertically.
can be used in the potentially explosive atmospheres of the following zones (accord-
ing to ATEX 94/9/EC):
- Zone 22
- Zone 1, category 2G or Zone 2, category 3G.
Requirement: The device must be mounted in a pressurized housing.
Max. permissible pressure: 10 mbar continuous.
15" devices with a stainless steel front:
- must only be mounted horizontally.
- can be used in potentially explosive atmospheres, Zone 22.
- require an additional set of retaining brackets for mounting in accordance with IP65
and for use in potentially explosive atmospheres. Please contact your supplier.
1
Select the mounting position of the device as described in Chapter 5.2.3 Requirements for the
mounting position,  26.
2
Prepare a mounting cutout for the device at the selected position:
Mounting cutout:
10.4" devices: 329 × 238 mm (±1 mm)
12.1" devices: 344 × 262 mm (±1 mm)
15" devices: 410 × 315 mm (±1 mm)
Material thickness at the mounting cutout 2...5 mm
329.0
+1/-1
Fig. 36 Mounting cutout for 10.4" devices
MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com
344.0
+1/-1
Fig. 37 Mounting cutout for 12.1" devices
5 Installation
5.4 Mounting
49