Output connection:
Before connecting the output make certain the UPS is off and there is no voltage on the output disconnector terminals.
- Connect the output line earth cable to the terminal on the base of the equipment.
- Connect the output line Neutral cable to its terminal on the output disconnector using a suitable cable terminal.
- Insert a copper plate between terminals L1out, L2out and L3out of the output disconnector.
- Connect the output line cable L1 to its terminal L1out of the output disconnector using a suitable cable terminal.
- Plug the EC15 connector into the backplane of each UPS tunnel as shown in the figure.
ATTENTION
The plate must be mounted in contact on the disconnector switch terminals with the cable terminals on top – and
not vice versa. In the single-phase output configuration the UPS could be seriously damaged if the EC15 connector
is not plugged in to each UPS backplane.
When connecting the output line take great care not to reverse the UPS cables that are already on the terminals of
the disconnector switch.
Archimod® 20kVA-40kVA Single-phase/Single-phase UPS - (without separate bypass line)
L1in
Nin
blue
brown
black
grey
brown
blue
Archimod®
blue
L1out
Nout
41