7. Control panel
Historical Data
7.2.2 UPS settings
Options
(*) Available in the "Service Mode" only
ATTENTION:
Please refer to paragraph 2.4 to set the CONFIG INVERTER parameter correctly.
56
®
UPS operation
With battery
Battery charger Op.
Tot. run downs
Booster Int.
Bypass Int.
Batt. Calibr.
Battery ch.Cycles
Batt.eq.cycles
>80% load N
>80% load T
>100% load N
>100% load T
Startup with Battery
Restart
Voltage
Frequency
Output
Inverter (*)
Phases in
start-up (**)
Total time the UPS has been working
Total time the UPS has been running on battery
Total time the battery charger has been working
Total number of times the batteries have been completely run down
Total number of Booster interventions
Total number of Bypass interventions
Total number of battery Calibrations
Total number of battery charger cycles
Total number of battery equalisation cycles
Total number of times the load has exceeded 80%
of nominal load
Total time the load has exceeded 80%
of the nominal load
Total number of times charging has exceeded 100%
of nominal load
Total time the load has exceeded 100%
of the nominal load without the overload being signalled
If enabled, it allows the UPS to be started when there is a power failure
If enabled, it allows automatic restarts
It sets the output voltage value [V]
It sets the output frequency value [Hz]
- Rated Value: it allows the output frequency value to be set (50 or 60
[Hz]) regardless of the supply voltage frequency.
- Automatic Select.: if enabled the UPS measures the input voltage
frequency and synchronises the output to the same value. If disabled
the UPS uses the Nominal Value as the setting.
It sets the output configuration and the load applied
- Single-phase: just one single-phase output
- Three-phase 120°: three-phase output suitable
for supplying three-phase loads (e.g. a motor)
- Three separate phases: three single-phase output lines
separate from each other
It allows the UPS start-up status to be programmed
Phase L1
for each output:
- Always on: phase always on in start-up;
Phase L2
- Always off: phase always off in start-up;
- Last status: phase restored to the status prior
Phase L3
to shutting down
(**) only available with the inverter configured with 3 independent phases