Choosing the
To get the most out of your FRONUS IG unit, observe the following rules:
location gene-
ral
- Limit grid impedance by using an appropriately-sized AC conductor
- Only install it on a solid vertical wall at a minimum of 3 ft. (0.9 m) above
- The ambient temperature should not be below -4 °F (-20 °C) or over
- No objects are to be located within a distance of 6 in. around the air
- Keep a distance of 8 in. minimum. For optimal airflow and cooling effi-
- The air flow direction within the inverter is from left to right (cold air
- When installing the FRONIUS IG unit in a switch panel cabinet (or
Choosing the
- during certain operation phases the FRONIUS IG unit may produce a
location
- the FRONIUS IG unit is not to be set up in areas with large amounts of
- the FRONIUS IG unit is not to be set up in areas with large amount of
- the FRONIUS IG unit is to be installed at a height that keeps the display
- NEMA 3R protection means that the FRONIUS IG can be exposed to
- In spite of the NEMA 3R protection system, the FRONIUS IG should not
between the FRONIUS IG unit and the in-house distribution panel. The
AC conductor cable resistance between the FRONIUS IG unit and the
house distribution panel should not exceed 0.5 Ohm. This can be achie-
ved by using the following cable-sizes (according to NEC handbook,
chapter 9, table 8):
- AWG 10: maximum 200 ft. (60 m)
- AWG 12: maximum 126 ft. (38 m)
the ground and to a maximum of 6.5 ft. (2 m)
122 °F (50 °C).
vents on both sides of the FRONIUS IG unit.
ciency in hot climates Fronius recommends a distance of 10 - 12 in.
between each inverter or anything to the right or left of the inverter such
as walls or DC and AC disconnects.
intake on left, hot air exit on right).
similar closed environment) it is necessary to make sure that the hot air
that develops will be discharged by forced ventilation.
slight noise. For this reason it should not be installed in an occupied
living area
dust. If unavoidable, place the FRONIUS IG in an appropriately rated
and ventilated box.
conducting dust particles (for example iron filings)
slightly below eye level for best possible readability of the display.
moisture. However, we recommend that direct moisture be avoided, if
possible.
be exposed to direct sunlight, as this could result in temperature dera-
ting.
43