Class 1

Definition of service class: First digit in code represents the category.
Service codes of service class 1 are typically temporary. Their cause lies
in the grid.
The first reaction of your FRONIUS IG unit is to disconnect from the grid.
Subsequently, the grid will be checked for the duration of the observation
period stipulated. If after the end of this period no further defect is identi-
fied, your FRONIUS IG unit resumes operating and feeding power into the
grid.
The following table lists a number of service codes with their respective
designation, description, and repair measures.
Code
101
104
107
108
Designation
Grid voltage not within
admissible range
Grid frequency not wi-
thin admissible range
No grid voltage detec-
ted
Islanding detected
61
Description
As soon as the grid voltage
has returned to admissible
range, FRONIUS IG resu-
mes feeding power into the
grid
As soon as grid frequency
has returned to admissible
range, FRONIUS IG resu-
mes feeding power into the
grid
As soon as the grid conditi-
ons have returned to admis-
sible range, FRONIUS IG
resumes feeding power into
the grid
As soon as grid frequency
has returned to admissible
range, FRONIUS IG resu-
mes feeding power into the
grid
Repair
Check grid voltage
If the service code per-
sists you should contact
your electrical contrac-
tor
Check grid frequency
If the service code per-
sists you should contact
your electrical contrac-
tor
Check grid connections
and fuses
If the service code does
not disappear you should
contact your installation
specialist
Check grid voltage
If the service code does
not disappear you should
contact your electrical
contractor