General
Protection devices
(continued)
Ground fault protection
DC reverse polarity protection
Islanding protection
Over temperature
Field adjustab-
Field adjustable trip points
le trip points
Nominal AC output voltage
(L1-L2)
Operating AC voltage range default
(L1-L2)
Adjustment range for voltage
(L1-L2)
Voltage trip limit accuracy (L1-L2)
Nominal output frequency
Operating frequency range
Adjustment range for frequency
Frequency trip limit accuracy
Reconnect time
Adjustment range for reconnect time
Operating AC voltage range (L-N)
Adjustment range for voltage (L-N)
Voltage trip limit accuracy (L-N)
Our product complies with the following standards and regulations:
The FRONIUS IG unit complies with the regulations for "Inverters, conver-
ters, and controllers for use in independent power systems" (UL 1741-
2005).
In particular, the following standards and regulations are complied with:
- UL 1741-2005 (safety)
- FCC Part 15, Class A & B, regulations (EMI)
- UL 1741-2005, IEEE 1547 & IEEE 1547.1 (Anti-islanding protection)
- NEC Art.690, UL 1741-2005 (Ground-fault detector and interrupter)
- ANSI/IEEE C62.41 (surge test in low voltage AC-Power circuits)
Because the FRONIUS IG follows these regulations and holds these
certifications, it should meet or exceed all requirements of inverters from
both code and utility officials (for conformity declaration documents see
the Annex).
IG 4000
internal GFDI, in accordance with UL 1741 and NEC Art. 690
internal; in accordance with UL 1741, IEEE 1547 and NEC
active cooling / output power derating
IG 4000
240 V
212 - 264 V
180 - 270 V
71
IG 5100
IG 4500-LV
internal diode
IG 5100
IG 4500-LV
240 V
212 - 264 V
183 - 229 V
180 - 270 V
180 - 240 V
+/- 1.5 %
60 Hz
59.3 - 60.5 Hz
57.0 - 60.5 Hz
+/- 0.02 Hz
305 s
001 - 999 s
106 - 132 V
60 - 144 V
+/- 1.5 %
208 V