TPI Temperature control software
Thermostats using TPI (Time Proportional Integral) control
algorithms will reduce the temperature swing that normally
occurs when using traditional bellows or thermally operated
thermostats. As a consequence, a TPI regulating thermostat will
maintain the comfort level far more efficiently than any
traditional thermostat.
When used with a condensing boiler, the TPI thermostat will help
to save energy as the control algorithm allows the boiler to
operate in condensing mode more consistently compared to
older types of thermostat.
Ÿ For Gas boilers set the TPI setting to 6 cycles per hour (default
setting)
Ÿ For Oil boilers set the TPI setting to 3 cycles per hour
Ÿ For Electric heating set the TPI setting to 12 cycles per hour
To adjust this setting go to the SET UP MENU and select TPI
CYCLES