Cleaning the heat exchanger

Specific tools:
Cleaning tool
See chapter Spare parts
Gas 110 Eco 65: Ref. 83, Reference: 52484,
Gas 110 Eco 115: Ref. 483, Reference: 58286.
Clean inside the exchanger using the specific tool.
Remove the residues from the bottom of the exchanger.
Rinse with water jet until the water in the siphon runs clean.
Check that there are no residues in the bottom of the
exchanger.
Cleaning the fan
Unscrew the 2 screws at the bottom of the fan
Remove the venturi.
Clean the fan with a nylon brush (do not disturb balancing clips).
Check that the openings are clear and that the impellers turn
easily.
Re-assemble the fan.
26/01/2009 - 300014883-001-F

Cleaning the siphon

Gas 110 Eco 65:
Unscrew the nut on the siphon from underneath the boiler
Turn the siphon 90° to the front to dislodge it from the support
lug.
Gas 110 Eco 115:
Unscrew the siphon from the siphon body from underneath the
boiler
Turn the siphon 90° to the front to dislodge it from the support
lug.
Put the siphon back in place on the support lug.
Carefully remove the siphon under the boiler (Danger of
splashing).
Clean the siphon with water.
Fill the siphon with water.
Re-assemble the siphon.
Put the siphon back in place on the support lug.
The siphon must always be filled with water
(Risk of damage to the boiler).
.
Setting the burner
See chapter Starting or restarting after a prolonged shutdown,
Setting the burner.