Cleaning The Burner - REMEHA Gas 110 Eco 115 Installation And Service Manual

Gas fired condensing boiler
Hide thumbs Also See for Gas 110 Eco 115:
Table of Contents

Advertisement

Operational mode
If the boiler requires cleaning, carry out the following maintenance
operations :
- Open the heating body,
- Clean the burner,
- Clean the heat exchanger using the tool provided,
Opening and closing the heating body
Remove the front panel of the casing.
Disconnect the following electrical connections:
- Ionization probe Ht lead and earth cable
- Fan
,
- Gas block
.
Unscrew the gas valve joint
Take out the air inlet silencer
Unscrew the 13 holding nuts on the inspection hatch
There is a 230 V electricity supply at the back of the fan
which must be disconnected (Marker
If the inspection hatch seal remains stuck, it is necessary
to replace it.
Remove the inspection hatch, fan, burner and gas block unit.
50
,
.
.
.
).
Gas 110 Eco 115 / 65
- Clean the fan,
- Clean the siphon,
- Close the heating body,
- Measure the combustion.
- Tilt the top of the unit until the burner comes out completely,
- Then remove the inspection hatch, the fan and the gas valve unit.
Carry out the cleaning operation.
Connect the rear connector before putting the hatch back in
place.
Close the heating body following the above procedure in
reverse order.

Cleaning the burner

Remove the 3 screws and the 3 holding lugs on the burner
Remove the burner.
Carry out a visual check on the general appearance of the
burner.
Carefully clean the burner with compressed air.
Put the burner and its fastenings back in place.
Replace radiation cover if required.
.
26/01/2009 - 300014883-001-F