5.27 Compressor Motor Lock

Applicable
All outdoor unit models
Models
E5
Error Code
Method of Error
Outdoor unit PCB takes the position signal from UVW line connected between the inverter and
Detection
compressor, and the error is detected when any abnormality is observed in the phase-current
waveform.
Error Decision
When the compressor motor does not operate even by starting it in forced startup mode.
Conditions
Supposed
 Compressor lock
Causes
 High differential pressure (0.5 MPa or more)
 UVW connection error
 Defective inverter circuit
 The stop valve is not opened.
Troubleshooting
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the stop
valve open?
YES
Check the connection wiring for
compressor M1C.
Is the
connection line
of the compressor
normal?
YES
Power OFF
Are wire
connections
made to phases U, V
and W in the proper
order and
manner?
YES
Are wire
connections
made according
to the wiring
diagram?
YES
A
Troubleshooting by Error Code
NO
Field factor
Open the stop valve.
NO
Replace the connection line,
and then securely connect the
connector.
NO
Make proper wire connections.
NO
Make proper wire connections.
W
U
V
237