HORIZONTAL TERMINATIONS
MINIMUM HORIZONTAL VENTING
6" (152 mm) VENT
TERMINATION CAP
IMPORTANT: The horizontal vent heat shield must be installed when using a 45-degree elbow to horizontally position the vent system.
Exception: corner installations
Kozy Heat Wall Pass-thru, #800-WPT (4-1/2" (114 mm) - 6-1/2" (165 mm) wall thickness) or #800-WPT2 (6-1/2" (165 mm) - 12-1/2" (318 mm) wall
thickness), must be used on all horizontal vent runs.
MAXIMUM HORIZONTAL VENTING
PIPE SECTION
45° ELBOW
NOTE: Page 26 has information on restrictor installation in conjunction with
venting installation. Page 51 has information on restrictor recommendations
depending on burner flame appearance and instructions on installation after
venting is completed.
VENTING
HORIZONTAL VENT
HEAT SHIELD
45° ELBOW
10 ft.
(3.05 m)
PAGE 23
(Horizontal)
NOTE: Horizontal sections require
1/4" (6 mm) rise for every 12" (305
mm) of travel.
CAUTION: This gas appliance must
not be connected to or joined with
any other chimney flue serving
another appliance.
TERMINATION CAP