Chapter 6 - GP RUN Mode and Errors

6.4.2 Error Message Details

n

SYSTEM ERRORS

Indicates a fault in the basic operations of the GP.
Following the error message, an error code, as shown below, will appear. Report
the error number and details on how the error developed to your local GP distribu-
tor.
u u u u u
SYSTEM ERROR ( 03 : x x )
An unrecoverable error occurred during screen data transfer.
u u u u u
SYSTEM ERROR ( x x x : x x x : x x x )
An unrecoverable error occurred during screen data transfer.
Possible Solutions
• Check if the GP's Power Cord and the Input signal line have been wired sepa-
rately from each other.
• Check that the FG line has been grounded correctly, according to your country's
standards.
• Re-send the screen data from the PC to the GP.
• If other types of communication errors, such as [RECIEVE DATA ERROR],
[PLC COM. ERROR], have also occurred, try to correct those problems also.
If the above mentioned methods do not solve the problem, please contact your
local GP distributor.
GP-377 Series Users Manual
03 : x x
x x x : x x x : x x x
6.4.1 Error Message List
Error No.
Constant Value
Error No. 3
Error No. 2
Error No. 1
6-15