FAULTS LINKED TO THE HYDRAULIC SYSTEM
FAULT
No
increase
temperature
with
boiler in operation
Condensation
boiler
Radiators
cold
winter
CAUTION!
The operations
specialised personnel.
The manufacturer will not be held liable and the
guarantee will not be valid if this condition is not
abided by.
Faults / Causes / Solutions
USE AND MAINTENANCE MANUAL
POSSIBLE CAUSES
in
1. Incorrect combustion adjustment.
2. Boiler / system dirty.
3. Insufficient boiler power.
Poor quality pellets
in
1. Incorrect temperature adjustment.
2. Inadequate fuel consumption.
1. Room thermostat (local or remote)
in
set too low. If remote thermostat,
check if it is faulty.
2. Circulation pump does not run
because
it
3. Circulation pump does not run.
4. Radiators have air in them
in italics
must be performed solely by
COMPACT 24 BOILER
1. Adjust the boiler to a higher
2. Check the recipe and/or technical
1. Set to a higher temperature or
2. Release the circulation pump by
has
seized
up.
3. Check the electrical connections of
4. Vent the radiators
Technical dept. - All rights reserved - Reproduction prohibited
REMEDIES
1. Check recipe and parameters.
2. Check and clean the boiler.
3. Make sure the boiler is correctly
sized for the system requirements.
4. Use quality pellets
temperature.
parameters.
replace if necessary. (if remote)
removing the plug and turning the
shaft with a screwdriver.
the circulation pump and replace if
necessary.