A7" Indoor Unit: Malfunction Of Swing Flap Motor (Ma) - Daikin REYQ72 Serveice Manual

R-410a heat recovery 60hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
" A7 " Indoor Unit:
2.5
A7
Remote
Controller
Display
Applicable
FXHQ only
Models
Method of
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction
When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing
flap motor is energized for a specified amount of time (about 30 seconds).
Decision
Conditions
Supposed
Causes
132
Malfunction of Swing Flap Motor (MA)
Defect of swing motor
Defect of connection cable (power supply and limit switch)
Defect of air flow direction adjusting flap-cam
Defect of indoor unit PC board
SiUS39-602
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents