Unit Capacity Overrides; Demand Limit - Daikin WGZ030DW Operating And Maintenance Manual

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

Hold Clear Reset Value =
High Pressure Unload set point – ["Initial Offset" + ["Step-Increase" x ["number of occurrence"-1]]]
Initial Offset & Step Increase
Condenser
Configuration
Water-Cooled
Air-Cooled
Example of Operation: Assume a packaged water-cooled WGZ unit with 4 compressors using R410A as the
refrigerant. Circuit number one is fully loaded (both compressors running) when that circuit's condenser
pressure exceeds the High Condenser Pressure Unload set point. Circuit number one will unload by turning
one of the two compressors off immediately. This circuit will not be allowed to load back up until its
condenser pressure decreases below the "Hold Clear @" value which is displayed on the "VIEW CIRCUIT 1
(1)" screen. Since this is the first High Condenser Pressure – Unload occurrence for that circuit, the circuit
will be allowed to load once the condenser pressure drops below the High Condenser Pressure Unload set
point minus 40 psi. If using default value (405 psi) this will be 365 psi. After some time, the condenser
pressure is allowed to decrease below this value and circuit number one is again allowed to load up. Again its
condenser pressure exceeds the High Condenser Pressure Unload set point and it unloads. Because this is the
second High Condenser Pressure – Unload occurrence for that circuit, the circuit will not be allowed to load
until the condenser pressure drops below the High Condenser Pressure Unload set point minus 50 psig (40
psi plus step-increase10psi). If using default values, this will be 355 psi. As you can see, for each occurrence
the discharge pressure must get lower and lower (based on Step-Increase value) before the circuit is allowed
to again load. This logic is intended to prevent excessive cycling of compressors.

Unit Capacity Overrides

The following conditions override the automatic capacity control when the chiller is in cool mode only.

Demand Limit

The maximum unit capacity can be limited by a 4 to 20 mA signal on the Demand Limit analog input.
This function is only enabled if the Demand Limit set point is set to ON. The maximum unit capacity
stage is determined as shown in the following graph.
Limit Signal vs. Max Stage
(with 4 compressors)
4
3
Max
Stage
2
1
0
4.0
8.0
Limit Signal (mA)
0
25.0
Limit Signal (%)
Any signal less than 4 mA does not limit the chiller capacity.
OMM 1130-2
No. of
R410A
Compressors
4
40 psi
6
32 psi
4
100 psi
6
80 psi
12.0
16.0
20.0
50.0
75.0
100.0
R22,
R134a
R407C
Increase
30 psi
30 psi
N/A
20 psi
70 psi
N/A
N/A
N/A
Limit Signal vs. Max Stage
(with 6 compressors)
6
5
4
Max
Stage
3
2
1
0
4.0
6.7
9.3
Limit Signal (mA)
0
16.7
33.3
Limit Signal (%)
Step
10 psi
10 psi
15 psi
15 psi
12.0
14.7 17.3
20.0
50.0
66.7 83.4
100.0
47